File access from the PLC
The use of the PLC function blocks for data access from the Tc2_system library is introduced in this example. A new function block, FB_FileCopy, is implemented with the aid of the existing function blocks. Using the FB_FileCopy function block, binary files can be copied in the local TwinCAT system or between a local and a remote TwinCAT system.
The complete source code for the example project can be unpacked from here: FileCopyExample.zip
![]() | Network drives cannot be accessed using the FB_FileCopy function block. |
A rising edge at the bExecute input of the FB_FileCopy block results in execution of the following steps.
a) Open the source and destination files
b) Read the source file into a buffer
c) Write the bytes that have been read from the buffer into the destination file
d) Check whether the end of the source file has been reached. If not, then repeat b) and c). If yes, then jump to e)
e) Close the source and destination files;
The file is copied one segment at a time. In this example, the size of the buffer has been specified as 1000 bytes, but this can be modified.
PLC program

Declaration Part
FUNCTION_BLOCK FB_FileCopy
VAR_INPUT
sSrcNetId : T_AmsNetId;
sSrcPathName : T_MaxString;
sDestNetId : T_AmsNetId;
sDestPathName : T_MaxString;
bExecute : BOOL;
tTimeOut : TIME := DEFAULT_ADS_TIMEOUT;
END_VAR
VAR_OUTPUT
bBusy : BOOL;
bError : BOOL;
nErrId : UDINT;
END_VAR
VAR
fbFileOpen : FB_FileOpen;
fbFileClose : FB_FileClose;
fbFileRead : FB_FileRead;
fbFileWrite : FB_FileWrite;
hSrcFile : UINT := 0;(* File handle of the source file *)
hDestFile : UINT := 0;(* File handle of the destination file *)
Step : DWORD;
RisingEdge : R_TRIG;
buffRead : ARRAY[1..1000] OF BYTE;(* Buffer *)
cbReadLength : UDINT := 0;
END_VARImplementation
RisingEdge(CLK:=bExecute);
CASE Step OF
0: (* Idle state *)
IF RisingEdge.Q THEN
bBusy := TRUE;
bError:= FALSE;
nErrId:=0;
Step := 1;
cbReadLength:=0;
hSrcFile:=0;
hDestFile:=0;
END_IF
1: (* Open source file *)
fbFileOpen( bExecute := FALSE );
fbFileOpen( sNetId := sSrcNetId, sPathName := sSrcPathName,
nMode := FOPEN_MODEREAD OR FOPEN_MODEBINARY,
ePath := PATH_GENERIC, tTimeout := tTimeOut, bExecute := TRUE );
Step := Step + 1;
2:
fbFileOpen( bExecute := FALSE );
IF NOT fbFileOpen.bBusy THEN
IF fbFileOpen.bError THEN
nErrId := fbFileOpen.nErrId;
bError := TRUE;
Step := 50;
ELSE
hSrcFile := fbFileOpen.hFile;
Step := Step + 1;
END_IF
END_IF
3: (* Open destination file *)
fbFileOpen( bExecute := FALSE );
fbFileOpen( sNetId := sDestNetId, sPathName := sDestPathName,
nMode := FOPEN_MODEWRITE OR FOPEN_MODEBINARY,
ePath := PATH_GENERIC, tTimeout := tTimeOut, bExecute := TRUE );
Step := Step+1;
4:
fbFileOpen( bExecute := FALSE );
IF NOT fbFileOpen.bBusy THEN
IF fbFileOpen.bError THEN
nErrId := fbFileOpen.nErrId;
bError := TRUE;
Step := 50;
ELSE
hDestFile := fbFileOpen.hFile;
Step := Step + 1;
END_IF
END_IF
5: (* Read data from source file *)
cbReadLength := 0;
fbFileRead( bExecute:= FALSE );
fbFileRead( sNetId:=sSrcNetId, hFile:=hSrcFile,
pReadBuff:= ADR(buffRead), cbReadLen:= SIZEOF(buffRead),
bExecute:=TRUE, tTimeout:=tTimeOut );
Step := Step + 1;
6:
fbFileRead( bExecute:= FALSE );
IF NOT fbFileRead.bBusy THEN
IF fbFileRead.bError THEN
nErrId := fbFileRead.nErrId;
bError := TRUE;
Step := 50;
ELSE
cbReadLength := fbFileRead.cbRead;
Step := Step + 1;
END_IF
END_IF
7: (* Write data to destination file *)
fbFileWrite( bExecute := FALSE );
fbFileWrite( sNetId:=sDestNetId, hFile:=hDestFile,
pWriteBuff:= ADR(buffRead), cbWriteLen:= cbReadLength,
bExecute:=TRUE, tTimeout:=tTimeOut );
Step := Step + 1;
8:
fbFileWrite( bExecute := FALSE );
IF NOT fbFileWrite.bBusy THEN
IF fbFileWrite.bError THEN
nErrId := fbFileWrite.nErrId;
bError := TRUE;
Step := 50;
ELSE
IF fbFileRead.bEOF THEN (* Check if the EOF flag ist set *)
Step := 50; (* Cleanup: close the destination and source files *)
ELSE
Step := 5; (* Repeat reading/writing *)
END_IF
END_IF
END_IF
30: (* Close the destination file *)
fbFileClose( bExecute := FALSE );
fbFileClose( sNetId:=sDestNetId, hFile:=hDestFile, bExecute:=TRUE, tTimeout:=tTimeOut );
Step := Step + 1;
31:
fbFileClose( bExecute := FALSE );
IF NOT fbFileClose.bBusy THEN
IF fbFileClose.bError THEN
nErrId := fbFileClose.nErrId;
bError := TRUE;
END_IF
Step := 50;
hDestFile := 0;
END_IF
40: (* Close source file *)
fbFileClose( bExecute := FALSE );
fbFileClose( sNetId:=sSrcNetId, hFile:=hSrcFile, bExecute:=TRUE, tTimeout:=tTimeOut );
Step := Step + 1;
41:
fbFileClose( bExecute := FALSE );
IF NOT fbFileClose.bBusy THEN
IF fbFileClose.bError THEN
nErrId := fbFileClose.nErrId;
bError := TRUE;
END_IF
Step := 50;
hSrcFile := 0;
END_IF
50: (* Error or ready => Cleanup *)
IF ( hDestFile <> 0 ) THEN
Step := 30; (* Close the destination file*)
ELSIF (hSrcFile <> 0 ) THEN
Step := 40; (* Close the source file *)
ELSE
Step := 0; (* Ready *)
bBusy := FALSE;
END_IF
END_CASE