FB_PN_IM1_READ

The PROFINET controller uses the function block FB_PN_IM1_READ to read all I&M1 (Information & Maintenance) data from a device referenced via the Port input. 
The frame structure of the I&M1 function corresponds to the index 0xAFF1 according to the PROFINET standard.
 Inputs
 Inputs
VAR_INPUT
  bStart  : BOOL;
  NETID   : T_AmsNetId;
  PORT    : T_AmsPort;
END_VAR| Name | Type | Description | 
|---|---|---|
| bStart | BOOL | The function block is enabled by a positive edge at this input. | 
| NETID | T_AmsNetId | AMS Net ID of the controller | 
| PORT | T_AmsPort | Port via which the controller communicates with the device (port = Device ID + 1000hex). | 
 Outputs
 Outputs
VAR_OUTPUT
  bBusy                   : BOOL;
  st_IM_TagFunction       : STRING(32);
  st_IM_TagLocation       : STRING(22);
  bError                  : BOOL;
  iErrorID                ; UDINT;
END_VAR| Name | Type | Description | 
|---|---|---|
| bBusy | BOOL | When the function block is enabled, this output is set and remains set until a feedback is received. While Busy = TRUE, no new command will be accepted at the inputs. | 
| st_IM_TagFunction | STRING | Label read for function of the device. | 
| st_IM_TagLocation | STRING | Label read for the installation location of the device. | 
| bError | BOOL | If an error occurs during the transmission of the command, this output is set after the bBusy output is reset. | 
| iErrorID | UDINT | Returns an ADS error number if bError output is set. | 
Requirements
| Development environment | Target platform | PLC libraries to include | 
|---|---|---|
| TwinCAT v3.1.4018 | PC or CX (x64, x86, ARM) | Tc2_ProfinetDiag |