Mechanical backlash

Mechanical backlash is the difference in position between a drive or an encoder and the load. Mechanical backlash arises due mechanical tolerances in the drivetrain. This causes a difference between the required and the actual position of the load. This is especially important when the direction of motion is reversed.

There are three types of mechanical backlash:

Positive backlash

Positive backlash occurs in systems where the measuring system is directly coupled to the drive. In this case the backlash exists between the drive and the load. When the direction of motion is reversed, the measuring system will detect a change in position before the load has moved. So the encoder, which here measures the position of the load indirectly, leads the actual position of the load. As a consequence, the load will not reach the set position, it will be shorten by the length of the backlash.

In the figure below, a movement from left to right is defined as a positive movement.

Mechanical backlash 1:

The encoder leads the load (e.g. machine table), so the measured encoder position, leads the actual position of the table. Therefore the table’s movement will be too short.

In this case enter a positive correction value for the backlash (= normal case).

Negative backlash

Negative backlash occurs in systems where a mechanical tolerance exists between the drive and the measuring system. When the direction of motion is reversed the load immediately moves in the new direction and the measuring system won’t detect the changed position. In this case the load will travel further than required. The encoder, which measures the position of the load directly, lags behind the actual position of the machine part.

Mechanical backlash 2:

The encoder lags behind the actual position of the load (e.g. machine table). Therefore the table will travel too far.

In this case enter a negative correction value for the backlash.

Neutral backlash

In systems, neutral backlash is an exception. In this case the measuring system is directly coupled to the load and electrically connected with the drive. Here the encoder position and the load position are the same. Now when the drive’s direction of motion is reversed, the backlash will be automatically compensated. The position control loop is closed around the drivetrain because the encoder is coupled to the load directly. The set position can be reached with no further compensation.

Mechanical backlash 3:
Mechanical backlash 4:

The encoder is directly coupled with the load (e.g. machine table) and ensuring steady state accuracy. No special settings are required.

General Hints and Notes: