FB_EcGetAllSlaveAbnormalStateChanges

The function block FB_EcGetAllSlaveAbnormalStateChanges can be used to read the unexpected EtherCAT state changes of all the slaves connected to the master. If the call is successful, the buffer transferred in the parameter pBufAddr contains the number of unexpected state changes of all slaves as an array of UDINTs. EtherCAT state changes are unexpected if they were not requested by the EtherCAT master, e.g. if an EtherCAT slave spontaneously switches from OP state to SAFEOP state.
Inputs
VAR_INPUT
sNetId : T_AmsNetId; (*AmsNetId of the EtherCAT master device*)
pAddrBuf : POINTER TO ARRAY [0..EC_MAX_SLAVES] OF UDINT;
(*Contains the address of the buffer the counters for the state changes f.i. Op to SafeOp-Err are copied to.*)
cbBufLen : UDINT; (*Size of the buffer pAddrBuf. The size of the buffer must be at least nSlave *4 Bytes *)
bExecute : BOOL; (*Function Block execution is triggered by a rising edge at this input*)
tTimeout : TIME; (*States the time before the function is cancelled.*)
END_VARName | Type | Description |
|---|---|---|
sNetId | T_AmsNetId | String containing the AMS network ID of the EtherCAT master device. (Type: T_AmsNetId) |
pAddrBuf | POINTER TO ARRAY [0..EC_MAX_SLAVES] OF UDINT | Address of an array of UDINTs, into which the number of unexpected state changes of the individual slaves is to be written. |
cbBufLen | UDINT | Maximum available buffer size (in bytes) for the data to be read |
bExecute | BOOL | The function block is activated by a positive edge at this input. |
tTimeout | TIME | Maximum time allowed for the execution of the function block. |
Outputs
VAR_OUTPUT
bBusy : BOOL;
bError : BOOL;
nErrId : UDINT;
nSlaves : UINT;