FB_SoEAX5000ReadActMainVoltage_ByDriveRef
The current peak value of the mains voltage for the AX5000 (P-0-0200) can be read with the FB_SoEAX5000ReadActMainVoltage_ByDriveRef function block.
Inputs
VAR_INPUT
stDriveRef : ST_DriveRef;
bExecute : BOOL;
tTimeout : TIME := DEFAULT_ADS_TIMEOUT;
END_VARName | Type | Description |
|---|---|---|
stDriveRef | ST_DriveRef | Reference to the drive. The reference to the drive can be linked directly to the PLC in the System Manager. To do this, an instance of the structure ST_PlcDriveRef must be allocated and the NetID must be converted from the byte array into a string (Type: ST_DriveRef). |
bExecute | BOOL | The function block is activated by a positive edge at this input. |
tTimeout | TIME | Maximum time allowed for the execution of the function block. |
Outputs
VAR_OUTPUT
bBusy : BOOL;
bError : BOOL;
iAdsErrId : UINT;
iSercosErrId : UINT;
dwAttribute : DWORD;
fActualMainVoltage : REAL;
END_VARName | Type | Description |
|---|---|---|
bBusy | BOOL | This output is set when the function block is activated, and remains set until feedback is received. |
bError | BOOL | This output is set after the bBusy output has been reset when an error occurs in the transmission of the command. |
iAdsErrId | UINT | Returns the ADS error code of the last executed command when the bError output is set. |
iSercosErrId | UINT | Returns the Sercos error of the last executed command in the event of a set bError output. |
dwAttribute | DWORD | Returns the attributes of the Sercos parameter. |
fActualMainVoltage | REAL | Returns the peak value of the current mains voltage of the AX5000 (e.g. 303.0 corresponds to 303.0 V). |
Sample
fbReadActMainVoltage : FB_SoEAX5000ReadActMainVoltage_ByDriveRef;
bReadActMainVoltage : BOOL;
fActualMainVoltage : REAL;
stPlcDriveRef AT %I* : ST_PlcDriveRef;
stDriveRef : ST_DriveRef;
IF bInit THEN
stDriveRef.sNetId := F_CreateAmsNetId(stPlcDriveRef.aNetId);
stDriveRef.nSlaveAddr := stPlcDriveRef.nSlaveAddr;
stDriveRef.nDriveNo := stPlcDriveRef.nDriveNo;
stDriveRef.nDriveType := stPlcDriveRef.nDriveType;
IF (stDriveRef.sNetId <> '') AND(stDriveRef.nSlaveAddr <> 0)THEN
bInit := FALSE;
END_IF
END_IF
IF bReadActMainVoltage AND NOT bInit
THEN fbReadActMainVoltage(
stDriveRef := stDriveRef,
bExecute := TRUE,
tTimeout := DEFAULT_ADS_TIMEOUT,
fActualMainVoltage=>fActualMainVoltage
);
IF NOT fbReadActMainVoltage.bBusy THEN
fbReadActMainVoltage(stDriveRef := stDriveRef, bExecute := FALSE);
bReadActMainVoltage := FALSE;
END_IF
END_IF