FB_SoEReadDcBusVoltage_ByDriveRef

FB_SoEReadDcBusVoltage_ByDriveRef 1:

With the FB_SoEReadDcBusVoltage_ByDriveRef function block, the DC-Bus voltage of the drive (S-0-0380) can be read.

FB_SoEReadDcBusVoltage_ByDriveRef 2: Outputs

VAR_OUTPUT
   bBusy         : BOOL;
   bError        : BOOL;
   iAdsErrId     : UINT;
   iSercosErrId  : UINT;
   dwAttribute   : DWORD;
   fDcBusVoltage : REAL;
END_VAR

Name

Type

Description

bBusy

BOOL

This output is set when the function block is activated, and remains set until feedback is received.

bError

BOOL

This output is set after the bBusy output has been reset when an error occurs in the transmission of the command.

iAdsErrId

UINT

Returns the ADS error code of the last executed command when the bError output is set.

iSercosErrId

UINT

Returns the Sercos error of the last executed command in the event of a set bError output.

dwAttribute

DWORD

Returns the attributes of the Sercos parameter.

fDcBusVoltage

REAL

Supplies the DC bus voltage of the drive.

Sample

VAR
   bInit                : BOOL;
   fbReadDcBusVoltage   : FB_SoEReadDcBusVoltage_ByDriveRef;
   bReadDcBusVoltage    : BOOL;
   fDcBusVoltage        : REAL;
   stPlcDriveRef AT %I* : ST_PlcDriveRef;
   stDriveRef           : ST_DriveRef;
END_VAR
IF bInit THEN
   stDriveRef.sNetId := F_CreateAmsNetId(stPlcDriveRef.aNetId);
   stDriveRef.nSlaveAddr := stPlcDriveRef.nSlaveAddr;
   stDriveRef.nDriveNo := stPlcDriveRef.nDriveNo;
   stDriveRef.nDriveType := stPlcDriveRef.nDriveType;
   IF (stDriveRef.sNetId <> '') AND (stDriveRef.nSlaveAddr <> 0) THEN
      bInit := FALSE;
   END_IF
END_IF

IF bReadDcBusVoltage AND NOT bInit THEN
   fbReadDcBusVoltage(stDriveRef := stDriveRef,
                      bExecute := TRUE,
                      tTimeout := DEFAULT_ADS_TIMEOUT,
                      fDcBusVoltage => fDcBusVoltage );

   IF NOT fbReadDcBusVoltage.bBusy THEN
      fbReadDcBusVoltage(stDriveRef := stDriveRef, bExecute := FALSE);
      bReadDcBusVoltage := FALSE;
   END_IF
END_IF

FB_SoEReadDcBusVoltage_ByDriveRef 3: Inputs

VAR_INPUT
    stDriveRef : ST_DriveRef; 
    bExecute   : BOOL; 
    tTimeout   : TIME := DEFAULT_ADS_TIMEOUT;
END_VAR

Name

Type

Description

stDriveRef

ST_DriveRef

Reference to the drive. The reference to the drive can be linked directly to the PLC in the System Manager. To do this, an instance of the structure ST_PlcDriveRef must be allocated and the NetID must be converted from the byte array into a string (Type: ST_DriveRef).

bExecute

BOOL

The function block is activated by a positive edge at this input.

tTimeout

TIME

Maximum time allowed for the execution of the function block.