CouplerReset

The function block CouplerReset can be used to execute a reset of the coupler via the 2-byte PLC interface. During a coupler reset, for example, the current terminal configuration is read in again by the coupler via the K-bus (terminal bus) and communication on the K-bus is reinitialized. Existing K-bus error messages for the coupler are reset. The STATE and CONTROL variables are used to perform a handshake with the coupler during the execution of the function block. These variables must therefore be linked to the Control/Status variables of the 2-byte PLC interface in the TwinCAT System Manager.
Inputs
VAR_INPUT
STATE : PLCINTFSTRUCT;
START : BOOL;
TMOUT : TIME;
END_VARName | Type | Description |
|---|---|---|
STATE | Status word of the 2-byte PLC interface. | |
START | BOOL | The function block is enabled by a positive edge at this input. |
TMOUT | TIME | Specifies the time-out period that must not be exceeded when the function is executed. |
Outputs
VAR_OUTPUT
CONTROL : PLCINTFSTRUCT;
BUSY : BOOL;
ERR : BOOL;
ERRID : UDINT;
END_VARName | Type | Description |
|---|---|---|
CONTROL | Control word of the 2-byte PLC interface. | |
BUSY | BOOL | When the function block is activated, this output is set and remains set until the function is completed. |
ERR | BOOL | If an error occurs during the execution of the function, this output is set after the BUSY output is reset. |
ERRID | UDINT | If the ERR output is set, this parameter supplies the error number. |
Error number | Error description |
|---|---|
0 | No error |
0x100 | Error during initialization of communication via the 2-byte PLC interface |
0x200 | Error during communication |
0x300 | Timeout error. The permitted execution time has been exceeded |
0x400 | Incorrect parameter value for register number |
0x500 | Incorrect parameter value for table number |
Example of a call in FBD:
VAR
IntfState AT%I* : PLCINTFSTRUCT;
IntfControl AT%Q* : PLCINTFSTRUCT;
CouplerReset1 : CouplerReset;
Start_CouplerReset : BOOL;
CouplerReset_Busy : BOOL;
CouplerReset_Err : BOOL;
CouplerReset_ErrId : UDINT;
END_VAR
The variables IntfState and IntfControl are linked with corresponding I/O variables in the TwinCAT System Manager.
Requirements
|
Development environment |
Target system type |
PLC libraries to include (category group) |
|---|---|---|
|
TwinCAT v3.1.0 |
PC or CX (x86, x64, ARM) |
Tc2_Coupler (IO) |