FB_MBReadInputs (Modbus function 2)
 
This function is used for reading 1 to 2048 digital inputs. One digital input corresponds to one bit of the read data bytes.
VAR_INPUT
VAR_INPUT
sIPAddr : STRING(15);
nTCPPort : UINT:= MODBUS_TCP_PORT;
nUnitID : BYTE:=16#FF;
nQuantity : WORD;
nMBAddr : WORD;
cbLength : UDINT;
pDestAddr : UDINT;
bExecute : BOOL;
tTimeout : TIME;
END_VAR
sIPAddr: Is a string containing the IP address of the target device.
nTCPPort: Port number of the target device.
nUnitID: Identification number of a serial sub-network device. If a device is addressed directly via TCP/IP, this value must be 16#FF.
nQuantity: Number of digital inputs (data bits) to be read. The value of nQuantity must be > 0.
nMBAddr: Start address of the digital inputs to be read (bit offset).
cbLength: Contains the max. byte size of the destination buffer. The minimum buffer byte size must be: (nQuantity + 7) / 8.
pDestAddr: Contains the address of the destination buffer into which the data are to be read. The buffer can be a single variable, an array or a structure, whose address can be found with the ADR operator.
bExecute: The function block is activated by a rising edge at this input.
tTimeout: States the length of the timeout that may not be exceeded by execution of the ADS command.
VAR_OUTPUT
VAR_OUTPUT
bBUSY : BOOL;
bError : BOOL;
nErrId : UDINT;
cbRead : UDINT;
END_VAR
bBusy : When the function block is activated this output is set. It remains set until an acknowledgement is received.
bError : If an ADS error should occur during the transfer of the command, then this output is set once the bBusy output is reset.
nErrId : Supplies the ADS error number when the bError output is set.
cbRead: Contains the number of bytes currently read.
Function specific ADS error code  | Possible reason  | 
|---|---|
0x8001  | Modbus function not implemented  | 
0x8002  | Invalid address or length  | 
0x8003  | Invalid parameters: - wrong number of registers  | 
0x8004  | Modbus server error  | 
Example of calling the block in FBD:
PROGRAM Test
VAR
fbReadInputs : FB_MBReadInputs;
bReadInputs : BOOL;
bReadInputsBusy : BOOL;
bReadInputsError : BOOL;
nReadInputsErrorId : UDINT;
nReadInputsCount : UDINT;
nQuantity : WORD := 20;
nMBAddr : WORD := 29;
arrData : ARRAY [1..3] OF BYTE;
END_VAR
 
After a rising edge of "bExecute" and successful execution of the ReadInputs command, the content of digital inputs 30 - 49 is written into the arrData array:
Digital outputs  | Array offset  | Status  | 
|---|---|---|
29-36  | 1  | 0x34 The status of inputs 36 is the MSB of this byte (left)  | 
37-44  | 2  | 0x56 The status of inputs 44 is the MSB of this byte (left)  | 
45-49  | 3  | 0x07 Since only 20 outputs are to be read, the remaining bits (5-8) are set to 0.  | 
Requirements
Development environment  | Target system type  | PLC libraries to be linked  | 
|---|---|---|
TwinCAT v2.8.0  | PC (i386)  | TcModbusSrv.Lib  |