Drive Errors
Error(hex) |
Error(dec) |
Error type |
Description | |
---|---|---|---|---|
4600 |
17920 |
Parameter |
‘"Drive ID not allowed" The value for the drive ID is not allowed, e.g. because it has already been assigned, is less than or equal to zero, or is greater than 255. | |
Value range: [1 ... 255] |
Unit: 1 | |||
4601 |
17921 |
Parameter |
‘Drive type impermissible’ The value for the drive type is impermissible, since it is not defined. | |
Value range: [1, 20] |
Unit: 1 | |||
4602 |
17922 |
Parameter |
‘Drive operating mode impermissible’ The value for the drive operating mode is impermissible (mode 1: standard). | |
Value range: [1] |
Unit: 1 | |||
4603 |
17923 |
Parameter |
"Motor polarity inverted?" The flag for the motor polarity is not allowed. Flag 0: Positive motor polarity flag 1: Negative motor polarity | |
Value range: [0, 1] |
Unit: 1 | |||
4604 |
17924 |
Parameter |
‘Drift compensation/speed offset (DAC offset)’ The value for the drift compensation (DAC offset) is impermissible. | |
Value range: [-100.0, 100.0] |
Unit: e.g. m/min | |||
4605 |
17925 |
Parameter |
‘Reference speed (velocity pre-control)’ The value for the reference speed (also called velocity pilot control) is impermissible. | |
Value range: [0.0, 10000.0] |
Unit: e.g. m/min | |||
4606 |
17926 |
Parameter |
‘Reference output in percent’ The value for the reference output in percent is impermissible. The value 1.0 (100 %) usually corresponds to a voltage of 10.0 V. | |
Value range: [0.0, 5.0] |
Unit: % | |||
4607 |
17927 |
Parameter |
‘Quadrant compensation factor’ The value for the quadrant compensation factor is impermissible. | |
Value range: [0.0, 100.0] |
Unit: 1 | |||
4608 |
17928 |
Parameter |
‘Velocity reference point’ The value for the velocity reference point in percent is impermissible. The value 1.0 corresponds to 100 percent. | |
Value range: [0.01, 1.0] |
Unit: % | |||
4609 |
17929 |
Parameter |
‘Output reference point’ The value for the output reference point in percent is impermissible. The value 1.0 corresponds to 100 percent. | |
Value range: [0.01, 1.0] |
Unit: % | |||
460A |
17930 |
Parameter |
‘Minimum or maximum output limits (output limitation)’ The value for the minimum and/or maximum output limit is impermissible. This will happen if the range of values is exceeded, the maximum limit is smaller than the minimum limit, or the distance between the minimum and maximum limits is zero. The minimum limit is initially set to –1.0 (-100 percent) and the maximum limit to 1.0 (100 percent). | |
Value range: [-1.0, 1.0] |
Unit: % | |||
460B |
17931 |
Parameter |
“DRIVEERR_RANGE_MAXINCREMENT” | |
460C |
17932 |
Parameter |
“DRIVEERR_RANGE_ DRIVECONTROLDWORD” | |
460D |
17933 |
Parameter |
“DRIVEERR_RANGE_ RESETCYCLECOUNTER” | |
460F |
17935 |
Parameter |
‘Drive torque output scaling impermissible’ The value is impermissible as drive torque output scaling (rotary motor) or as force output scaling (linear motor). | |
Value range: [0, 1000000] |
Unit: 1 | |||
4610 |
17936 |
Parameter |
„Drive velocity output scaling is not allowed“ The value for the drive velocity output scaling is not allowed. | |
Value range: [0, 1000000] |
Unit: 1 | |||
4611 |
17937 |
Parameter |
‘Profi Drive DSC proportional gain Kpc (controller) impermissible’ Positions The value for the Profi Drive DSC position control gain (Kpc factor) is impermissible. | |
Value range: [0, 0xFFFFFF] |
Unit: 0.001 * 1/s | |||
4612 |
17938 |
Parameter |
‘Table ID is impermissible’ The value for the table ID is impermissible. | |
Value range: [0, 255] |
Unit: 1 | |||
4613 |
17939 |
Parameter |
‘Table interpolation type is impermissible’ The value is impermissible as the table interpolation type. | |
Value range: 0 (LINEAR), 2 (SPLINE) |
Unit: 1 | |||
4614 |
17940 |
Parameter |
‘Output offset in percent is impermissible’ The value is impermissible as an output offset in percent (+/- 1.0). | |
Value range: [-1.0, 1.0] |
Unit: % | |||
4615 |
17941 |
Parameter |
‘Profi Drive DSC scaling for calculation of “Xerr” (controller) impermissible’ Positions: the value is impermissible as Profi Drive DSC scaling for the calculation of ‘Xerr’. | |
Value range: [0, 1000000] |
Unit: 1 | |||
4616 |
17942 |
Parameter |
‘Drive acceleration output scaling impermissible’ The value is impermissible as drive acceleration/deceleration output scaling. | |
Value range: [0, 1000000] |
Unit: 1 | |||
4617 |
17943 |
Parameter |
‘Drive position output scaling impermissible’ The value is impermissible as drive position output scaling. | |
Value range: [0, 1000000] |
Unit: 1 | |||
461C |
17948 |
Parameter |
‘Drive filter type impermissible for command variable filter for the output position’ The value is impermissible as a drive filter type for the smoothing of the output position (command variable filter for the setpoint position). | |
Value range: [0, 2] |
Unit: 1 | |||
461D |
17949 |
Parameter |
‘Drive filter time impermissible for command variable filter for the output position’ The value is impermissible as a drive filter time for the smoothing of the output position (command variable filter for the setpoint position). | |
Value range: [0.0, 1.0] |
Unit: s | |||
461E |
17950 |
Parameter |
‘Drive filter order impermissible for command variable filter for the output position’ The value is impermissible as a drive filter order (P-Tn) for the smoothing of the output position (command variable filter for the setpoint position). | |
Value range: [0, 10] |
Unit: 1 | |||
4620 |
17952 |
Parameter |
‘Bit mask for stepper motor cycle impermissible’ A value of the different stepper motor masks is impermissible for the respective cycle. | |
Value range: [0, 255] |
Unit: 1 | |||
4621 |
17953 |
Parameter |
‘Bit mask for stepper motor holding current impermissible’ The value for the stepper motor holding mask is impermissible. | |
Value range: [0, 255] |
Unit: 1 | |||
4622 |
17954 |
Parameter |
‘Scaling factor for actual torque (actual current) impermissible’ The value is impermissible as a scaling factor for the actual torque (or actual current). | |
Value range: [0, 1E+30] |
Unit: | |||
4623 |
17955 |
Parameter |
‘Filter time for actual torque is impermissible’ The value is impermissible as a filter time for the actual torque (or the actual current) (P-T1 filter). | |
Value range: [0.0, 60.0] |
Unit: s | |||
4624 |
17956 |
Parameter |
‘Filter time for the temporal derivation of the actual torque is impermissible’ The value is impermissible as a filter time for the temporal derivation of the actual torque (or actual current (P-T1 filter). | |
Value range: [0.0, 60.0] |
Unit: s | |||
4627 |
17959 |
Function |
DRIVEOPERATIONMODEBUSY. The activation of the drive operation mode failed, because another object with OID ... is already using this interface. | |
0x4630 ... 0x463F: Error codes are reserved for external drive errors (e.g. stepper motor terminal or ‘MC_PowerStepper’ function block) | ||||
4630 |
17968 |
Monitoring |
‘Overtemperature’ Overtemperature was detected or reported in the drive or terminal. | |
4631 |
17969 |
Monitoring |
‘Undervoltage’ Undervoltage was detected or reported in the drive or terminal. | |
4632 |
17970 |
Monitoring |
‘Wire break in phase A’ A wire break in phase A was detected or reported in the drive or terminal. | |
4633 |
17971 |
Monitoring |
‘Wire break in phase B’ A wire break in phase B was detected or reported in the drive or terminal. | |
4634 |
17972 |
Monitoring |
‘Overcurrent in phase A’ Overcurrent was detected or reported in phase A in the drive or terminal. | |
4635 |
17973 |
Monitoring |
‘Overcurrent in phase B’ Overcurrent was detected or reported in phase B in the drive or terminal. | |
4636 |
17974 |
Monitoring |
‘Torque overload (stall)’ A torque overload (stall) was detected or reported in the drive or terminal. | |
4640 |
17984 |
Initialization |
‘Drive initialization’ Drive has not been initialized. Although the drive has been created, the rest of the initialization has not been performed (1. Initialization of drive I/O, 2. Initialization of drive, 3. Reset drive). | |
4641 |
17985 |
Address |
‘Axis address’ Drive does not know its axis, or the axis address has not been initialized. | |
4642 |
17986 |
Address |
‘Address IO input structure’ Drive has no valid IO input address in the process image. | |
4643 |
17987 |
Address |
‘Address IO output structure’ Drive has no valid IO output address in the process image. | |
4650 |
18000 |
Monitoring |
‘Drive hardware not ready to operate’ The drive hardware is not ready for operation. The following are possible causes: | |
4651 |
18001 |
Monitoring |
Error in the cyclic communication of the drive (Life Counter). Reasons for this could be an interrupted fieldbus or a drive that is in the error state. | |
4652 |
18002 |
Monitoring |
‘Changing the table ID when active controller enable is impermissible’. Changing (deselecting, selecting) the characteristic curve table ID is not permissible when the controller enable for the axis is active. | |
4655 |
18005 |
Monitoring |
‘Invalid IO data for more than ‘n’ continuous NC cycles’ The axis (encoder or drive) has detected invalid IO data (e.g. n=3) for more than ‘n’ continuous NC cycles (NC SAF task). |