General NC Errors
Error(Hex) |
Error(Dec) |
Error Type |
Description |
---|---|---|---|
4000 |
16384 |
Internal |
"Internal error" Internal system error in the NC on ring 0, no further details. |
4001 |
16385 |
Memory |
"Memory error" The ring-0 memory management is not providing the required memory. This is usually a result of another error, as a result of which the controller will halt normal operation (now if not before). |
4002 |
16386 |
Internal |
"Nc retain data error (persistent data)" Error while loading the Nc retain data. The axes concerned are no longer referenced (status flag "Homed" is set to FALSE). |
4003 |
16387 |
Parameter |
Parameter for Monitoring the NC Setpoint Issuing is Invalid The parameter for activating or deactivating the function “cyclic monitoring of |
4004 |
16388 |
Internal |
External Error This error code can be set by an external module (e.g. third-party module) or can be set when an external module exhibits an error. |
4010 |
16400 |
Parameter |
"Channel identifier not allowed" Either an unacceptable value (not 1...255) has been used, or a channel that does not exist in the system has been named. |
4011 |
16401 |
Parameter |
"Group identifier not allowed" Either an unacceptable value (not 1...255) has been used, or a group that does not exist in the system has been named. |
4012 |
16402 |
Parameter |
"Axis identifier not allowed" Either an unacceptable value (not 1...255) has been used, or an axis that does not exist in the system has been named. |
4013 |
16403 |
Parameter |
"Encoder identifier not allowed" Either an unacceptable value (not 1...255) has been used, or a encoder that does not exist in the system has been named. |
4014 |
16404 |
Parameter |
"Controller identifier not allowed" Either an unacceptable value (not 1...255) has been used, or a controller that does not exist in the system has been named. |
4015 |
16405 |
Parameter |
"Drive identifier not allowed" Either an unacceptable value (not 1...255) has been used, or a drive that does not exist in the system has been named. |
4016 |
16406 |
Parameter |
"Table identifier not allowed" Either an unacceptable value (not 1...255) has been used, or a table that does not exist in the system has been named. |
4020 |
16416 |
Internal |
"No process image" No PLC-axis interface during creation of an axis. |
4021 |
16417 |
Internal |
"No process image" No axis-PLC interface during creation of an axis. |
4022 |
16418 |
Internal |
"No process image" No encoder-I/O interface during creation of an axis. |
4023 |
16419 |
Internal |
"No process image" No I/O-encoder interface during creation of an axis. |
4024 |
16420 |
Internal |
"No process image" No drive-I/O interface during creation of an axis. |
4025 |
16421 |
Internal |
"No process image" No I/O-drive interface during creation of an axis. |
4030 |
16432 |
Internal |
"Coupling type not allowed" Unacceptable master/slave coupling type. |
4031 |
16433 |
Internal |
"Axis type not allowed" Unacceptable type specification during creation of an axis. |
4032 |
16434 |
Parameter |
Unknown Channel Type The |
4040 |
16448 |
Internal |
"Axis is incompatible" Axis is not suitable for the intended purpose. A high speed/low speed axis, for example, cannot function as a slave in an axis coupling. |
4050 |
16464 |
Internal |
"Channel not ready for operation" The channel is not complete, and is therefore not ready for operation. This is usually a consequence of problems at system start-up. |
4051 |
16465 |
Internal |
"Group not ready for operation" The group is not complete, and is therefore not ready for operation. This is usually a consequence of problems at system start-up. |
4052 |
16466 |
Internal |
"Axis not ready for operation" The axis is not complete, and is therefore not ready for operation. This is usually a consequence of problems at system start-up. |
4060 |
16480 |
Internal |
"Channel exists" The channel that is to be created already exists. |
4061 |
16481 |
Internal |
"Group exists" The group that is to be created already exists. |
4062 |
16482 |
Internal |
"Axis exists" The axis that is to be created already exists. |
4063 |
16483 |
Internal |
"Table exists" The table that is to be created already exists, resp. it is tried internally to use an already existing table id ( e.g. for the universal flying saw). |
4070 |
16496 |
Internal |
"Axis index not allowed" The location within the channel specified for an axis is not allowed. |
4071 |
16497 |
Internal |
"Axis index not allowed" The location within the group specified for an axis is not allowed. |