Definition of file names
With that command in NC program file names can be defined, which are used from specific NC functions for example for the creation of a report file or for the call of a NC program.
#FILENAME [ <file_id>"<filename>" { <file_id>"<filename>" } ] (modal)
<file_id> File identification
file id's | Significance |
|---|---|
MSG | Name of the report file for #MSG SAVE. Default name is "message.txt". |
M6 | Name of the global sub program for implicit program call at M6 in NC program. The name is valid until M30. M6 is not used as M function anymore! Default name is set in[1]-43. |
G80 G89 | Name of the global sub programs for implicit program calls at G80 G89 in NC program. The names are valid until M30. Default names are set in[1]-45. |
G800- G819 | Name of the global sub programs for additional implicit program calls at G800 G819 in NC program. The names are valid until M30. Default names are set in[1]-46. |
Optional an equation sign (=) can be programmed between <file_id> and <filename>. The file names can be defined or changed in NC programe with #FILENAME at any time.
The file names are set on the default name at RESET and NC program start.
Programming examples
%example1
N10 #FILENAME[ MSG="prog_flow.txt" ]
N20 $IF V.E.PLC_START_HOME == 1
N30 G74 X1 Y2 Z3
N40 #MSG SAVE["Homing executed"] Output in prog_flow.txt
N50 $ENDIF
:
Nxx #MSG SAVE["Roughing OK"]
:
Nxx #MSG SAVE["Finishing OK"]
N985 V.E.WP_CNTR = V.E.WP_CNTR+1
N990 #MSG SAVE["Workpiece No. %d OK", V.E.WP_CNTR]
M1000 M30
%example2
N10 #FILENAME[ M6="tool_change.nc" ]
N20 G00 X100 Y100 Z0
N30 M6 Call of tool change program tool_change.nc
:
M1000 M30
%example3
N10 #FILENAME[ G80="g80_up_test.nc" ]
N20 G00 X100 Y100 Z50
N30 G80 Call of sub program g80_up_test.nc
:
M1000 M30
%example4
N10 #FILENAME[ G800="g800_up_test.nc" G815="g815_up_test.nc"]
N20 G00 X100 Y100 Z50
N30 G800 Call of sub program g800_up_test.nc
:
N90 G815 Call of sub program g815_up_test.nc
:
M1000 M30