Presetting of offset limits

#SET OFFSET [ <neg_offset>, <pos_offset> ] <axis_name> 

<neg_offset> Negative offset value. Must be programmed <0

<pos_offset> Positive offset value. Must be programmed >0

<axis_name> Axis, for which the offset limit shall be valid.

With this command the positive and the negative limits for the permissible manual operation offset can be set for the respective axis. Axes that are operated as rotatory modulo axis or spindles (M3, M4, M5, M19, S...) are not considered in this command. These offset limits are valid for all manual operating modes. The negative offset value must be smaller or equal to zero, the positive offset value greater or equal to zero. The offset values can be overwritten at any time without having previously programmed G202. The offset values can also be preset via parameter data record [2]-6/-7 of the axis. Further verifications, for example, checking for exceedings of permissable ranges are not realized.