Adding / Subtracting Offsets
The V.G.NP[j].ALL variable makes it possible that complete zero offset data records can newly be assigned by an additive allocation of existing zero offsets. The offsets of all axes are included in the individual calculations. The notations ` += `, ` -= `, and `=` are permitted in zero offset allocation.
Programming example 1
G54 (NPV1) has the combination of G55 (NPV2) and G57 (NPV4) allocated:
N10 V.G.NP[1].ALL = V.G.NP[2].ALL + V.G.NP[4].ALLProgramming example 2
The same operation; G54 is additionally included:
N10 V.G.NP[1].ALL = V.G.NP[1].ALL + V.G.NP[2].ALL + V.G.NP[4].ALLor
N10 V.G.NP[1].ALL += V.G.NP[2].ALL + V.G.NP[4].ALLNotice | |
Interconnecting V.G.NP[j].ALL variables with axis-related V.G.NP[j].V[i] variables or constants within an assignment is not possible! |
Programming example
G54 (NPV1) is defined by the combination of G55 (NPV2), the X offset of G57 (NPV4), and a correction value:
INCORRECT:
N10 V.G.NP[1].ALL = V.G.NP[2].ALL + V.G.NP[4].V.X + 100CORRECT:
The assignment must be made in two steps
N10 V.G.NP[1].ALL = V.G.NP[2].ALL
N20 V.G.NP[1].V.X = V.G.NP[4].V.X + 100