Path /Time related feed interpolation (G193/G293)

Path /Time related feed interpolation (G193/G293) 1:

The path related feed interpolation is only active combined with linear slope or slope type 3 (HSC slope).
The time related feed interpolation is only active combined with linear slope.

G193 Path related feed interpolation (non-modal)
G293 Time related feed interpolation (nicht modal)

With G193/G293 the feed rate between the initial and the programmed end velocity is linearly interpolated.

Programming example

N10 G01 X500 F1000 
N20 G193 X900 F400
N30 X1000 F400

At block-transition N10 / N20 the path related feed interpolation is actuated and deceleration to the end velocity is done linearly through the path programmed in N20.

Path /Time related feed interpolation (G193/G293) 2:Fig.20: Fig. 4.18: Path related feed interpolation with G193

Override changes are superimposed under consideration of the permissible axis dynamics.

Path /Time related feed interpolation (G193/G293) 3:

The programming of G193 with G293, G08 or G09 in the same NC-block is not permissible.

Programming example

N10 G01 X500 F1000 
N20 G293 X900 F400
N30 X1000 F400

At block-transition N10 / N20 the time related feed interpolation is actuated and deceleration to the end velocity is done linearly through the time.

Path /Time related feed interpolation (G193/G293) 4:Fig.21: Fig. 4.19: Time related feed interpolation with G293
Path /Time related feed interpolation (G193/G293) 5:

The programming of G293 with G193, G08 or G09 in the same NC-block is not permissible.