Maximum permissible absolute radius difference (P-CHAN-00171)
The permissible absolute radius difference of the circle radii between the starting point and the destination point is defined via the "max_radius_diff_circle" parameter. If the radius difference of a programmed circle is under the limit defined by P-CHAN-00171, starting from the starting radius the circle radius is transferred in a linear fashion to the destination radius; - otherwise, an error message is issued. If the parameter is not assigned or is assigned the value 0, the function is inactive.
| |
P-CHAN-00171 is active only when circle center point compensation is inactive (G164) |
Variable name | Type | Permitted range | Dimension |
|---|---|---|---|
max_radius_diff_circle | UNS32 | 0 < max_radius_diff_circle < 10000 | 0.1 µm |
EXAMPLE: The circle radius error may amount to 0.01mm. The parameter must be assigned the value 100.
Extract from channel parameters list:
# Permissible absolute radius difference in 0.1 µm
max_radius_diff_circle 100