ST_BACnet_FrameStatistics

Structure with information on BACnet frames.

TYPE ST_BACnet_FrameStatistics :
STRUCT
  confirmed              : ARRAY[0..29] OF ST_BACnet_ConfirmedServiceDiag;
  unConfirmed            : ARRAY[0..9] OF ST_BACnet_UnConfirmedServiceDiag;
  nSegmSendTimeouts      : DWORD;
  nFrameAllocFailCnt     : DWORD;
  nFrameSendCnt          : DWORD;
  nFrameSendFailCnt      : DWORD;
  nFrameRecvCnt          : DWORD;
  nFrameRecvFailCnt      : DWORD;
  nLinkStatusChangedCnt  : DWORD;
END_STRUCT
END_TYPE

nSegmSendTimeouts: Timeout during receipt of acknowledgement of segmented packages (remote station does not acknowledge a segmented response, segmented ACK)

nFrameAllocFailCnt: Number of lost frames due to problems with memory allocation (no free memory).

nFrameSendCnt: Number of sent frames.

nFrameSendFailCnt: Number of failed frames.

nFrameRecvCnt: Number of received frames.

nFrameRecvFailCnt: Number of faulty received frames.

nLinkStatusChangedCnt: Frequency of network status changes (cable pulled/link lost, cable plugged/link OK).