F_BACnet_RealGT

Function for comparing two floating-point values taking into account the value range. This function should be used instead of the standard operators (">" or "GT") for values from BACnet, since otherwise a PLC stop is triggered if the values to be compared are not in the finite range.

F_BACnet_RealGT 1:

VAR_INPUT

fIn1         : REAL;
fIn2         : REAL;

Return value: TRUE = value 1 is greater than value 2. FALSE = value 2 is smaller or equal value 1, or one of the two values is not in the finite value range.