F_BACnet_RealGE
Function for comparing two floating-point values taking into account the value range. This function should be used instead of the standard operators (">" or "GE") for values from BACnet, since otherwise a PLC stop is triggered if the values to be compared are not in the finite range.
 
 
VAR_INPUT
fIn1 : REAL;
fIn2 : REAL;
Return value: TRUE = value 1 is equal or greater than value 2. FALSE = value 2 is smaller than value 1, or one of the two values is not in the finite value range.