F_BACnet_RealNothing : DWORD
![F_BACnet_RealNothing : DWORD 1:](Images/png/12749638667__Web.png)
![F_BACnet_RealNothing : DWORD 2:](Images/png/12749640331__Web.png)
Application
Function returns the floating-point value "Not aNumber", encoded as DWORD. Process data of property Present_Value of AnalogValue and output objects, which are described with the encoded value Nothing, are not processed by the BACnet stack from Revision 12 (Nothing → do-nothing state).
Return value: "Not a number" or #QNAN (0x7FFFFFFF).