BAC_AC_SpRmTH_04

Application

The template BAC_AC_SpRmTH_04 is a set value program for an air conditioning plant with room or extract air cascade control for temperature and humidity.

There are two basic room temperature set values (SpTHtgY1, SpTColY1), with an energy-neutral zone between the lower set value (heating mode) and the upper set value (cooling mode). The energy-neutral zone is monitored via the function SpHSupVis.
An outside temperature-dependent offset of the basic room temperature set values is realised via two curve functions (summer/winter compensation).

BAC_AC_SpRmTH_04 1:

The relative room humidity set values (%) are entered via the BACnet AV objects SpHHumf (humidification) and SpHDehumf (dehumidification). There is an energy-neutral zone between the lower set value (humidification) and the upper set value (dehumidification), which is monitored via the function SpHSupVis.

The two set values for the relative room humidity are converted within the template via the current room temperature to two set values for the absolute room humidity (g/kg), SpXHumf (humidification) and SpXDehumf (dehumidification).

Interface

BAC_AC_SpRmTH_04 2:

System diagram

BAC_AC_SpRmTH_04 3:

Block diagram

BAC_AC_SpRmTH_04 4:

VAR_Input

rRmT     : REAL;  

rRmT: Measured value of the room temperature

VAR_OUTPUT

rSpTHtg        : REAL;  
rSpTCol        : REAL;  
rSpXHumf       : REAL;
rSpXDehumf     : REAL;
rSpHHumf       : Real;
rSpHDehumf     : Real;

rSpTHtg: Calculated heating set value for the room temperature

rSpTCol: Calculated cooling set value for the room temperature

rSpXHumf: Calculated set value absolute humidity; humidification

rSpXDehumf: Calculated set value absolute humidity; dehumidification

rSpHHumf: Set value relative humidity; humidification

rSpHDehumf: Set value relative humidity; dehumidification

Program description

Instance

Type

Task

SpTColX1

FB_BACnetAVSetpoint

Input of the value for interpolation point SpTColX1 cooling

SpTColX2

FB_BACnetAVSetpoint

Input of the value for interpolation point SpTColX2 cooling

SpTColY1

FB_BACnetAVSetpoint

Input of the value for interpolation point SpTColY1 cooling. The value is the base cooling setpoint value

SpTColY2

FB_BACnetAVSetpoint

Input of the value for interpolation point SpTColY2 cooling

SpTColScale

FB_BA_Chrct04

The function block calculates the characteristic cooling set value curve for the current room temperature, depending on the outside temperature.

BAC_AC_SpRmTH_04 5:

SpTCol

FB_BACnetAVDisplay

Output of the calculated room temperature cooling set value

SpTHtgX1

FB_BACnetAVSetpoint

Input of the value for interpolation point SpTHtgX1 heating

SpTHtgX2

FB_BACnetAVSetpoint

Input of the value for interpolation point SpTHtgX2 heating

SpTHtgY1

FB_BACnetAVSetpoint

Input of the value for interpolation point SpTHtgY1 heating. The value is the base heating setpoint value

SpTHtgY2

FB_BACnetAVSetpoint

Input of the value for interpolation point SpTHtgY2 heating

SpTHtgScale

FB_BA_Chrct04

The function block calculates the characteristic heating set value curve for the current room temperature, depending on the outside temperature.

BAC_AC_SpRmTH_04 6:

SpTHtg

FB_BACnetAVDisplay

Output of the calculated room temperature heating set value

SpTSupVis

FB_BA_SpSupVis

The function block is used for controlling the energy-neutral zone between the two set values SpTCol and SpTHtg

SpHHumf

FB_BACnetAVSetpoint

Input of the relative room humidity set value for humidification (%).

SpHDehumf

FB_BACnetAVSetpoint

Input of the relative room humidity set value for dehumidification (%).

SpHSupVis

FB_BA_SpSupVis

The function block is used for controlling the two set values SpHDehumf and SpHHumf

SpXHumf_HX

FB_BA_HX

This function block is used to calculate the set value for the absolute room humidity (humidification). For calculating the value, the room temperature, the set value for the relative humidity SpHHumf and the barometric air pressure are required.

SpXHumf

FB_BACnetAVDisplay

Output of the calculated absolute room humidity set value for humidification (g/kg).

SpXDehumf_HX

FB_BA_HX

This function block is used to calculate the set value for the absolute room humidity (dehumidification). For calculating the value, the room temperature, the set value for the relative humidity SpHDehumf and the barometric air pressure are required.

SpXDehumf

FB_BACnetAVDisplay

Output of the calculated absolute room humidity set value for dehumidification (g/kg).

Version history

Version number

Comments

1.0.1

First release