"Index offset" specification for encoder functions (Index group 0x5200 + ID)

Index offset

(Hex)

Access

Group type

Data type

Phys. unit

Definition range

Description 

Remarks

0x0000001A

Write

every

{

 

 

Set actual position encoder/axis

Base Unit

UINT32

ENUM

s. appendix

Actual position type (s. appendix)

REAL64

mm

±∞

Actual position for encoder/axis

caution by using!

}

 

 

 

0x0000001B

Write

every

void

 

 

Re-initialization of the actual encoder position

Note: Only takes effect for reference system “ABSOLUTE (with single overflow)”

From TC 2.11R3 Build 2261

 

 

 

 

 

 

 

 

0x00000200

Write

Function group "TouchProbeV2":

- SERCOS (SoE),

- EtherCAT (CANopen DS402)

- SoftDrive (TCom)

{

 

 

Activate "Touch Probe" (external latch)

From TC 2.11 Build 154

Only for SAF-port 501

UINT32

1

[1,2,3,4]

Probe unit

(probe 1, 2, 3, 4)

UINT32

1

[0,1]

Signal edge

(0=rising edge, 1=falling edge)

UINT32

1

[1,2]

Probe mode

(1=single, 2=continuous, ...)

UINT32

 

 

Reserved (e.g. signal source)

UINT32

 

 

Reserved

UINT32

 

 

Reserved

} 24 bytes

 

 

 

0x00000201

Write

KL5101,
SERCOS,
AX2xxx,
PROFIDrive

VOID

 

 

Activate "External latch" or
Activate "Measuring sensor function"

(typically rising edge)

 

0x00000201

Write

CANopen

UINT32[4]

 

 

Activate "External Latch"  1 to 4 or
Activate "Measuring sensor function" 1 to 4

(typically rising edge)

 

0x00000202

Write

KL5101,
AX2xxx,
PROFIDrive

VOID

 

 

Activate  "External Latch" or Activate "Measuring sensor function"

(falling edge)

 

0x00000202

Write

CANopen

UINT32[4]

 

 

Activate  "External Latch" 1 to 4 or Activate "Measuring sensor function" 1 to 4

(falling edge)

 

0x00000205

Write

Function group "TouchProbeV2":

- SERCOS (SoE),

- EtherCAT (CANopen DS402)

- SoftDrive (TCom)

{

 

 

Deactivate "Touch Probe" (external latch)

From TC 2.11 Build 1547

only for SAF-port 501

UINT32

1

[1,2,3,4]

Probe unit (probe 1, 2, 3, 4)

UINT32

1

[0,1]

Signal edge (0=rising edge, 1=falling edge)

UINT32

 

 

Reserved

UINT32

 

 

Reserved

UINT32

 

 

Reserved

UINT32

 

 

Reserved

} 24 byte

 

 

 

0x00000205

Write

KL5101,
SERCOS,
AX2xxx,
PROFIDrive

VOID

 

 

Deactivate  "External Latch" or Deactivate "Measuring sensor function"

 

0x00000205

Write

CANopen

UINT32[4]

 

 

Deactivate  "External Latch" or Deactivate "Measuring sensor function"

 

 

 

 

 

 

 

 

 

0x00000210

Write

KL5101,
SERCOS,
AX2xxx,
PROFIDrive

REAL64

e.g. mm

±∞

Set "External latch event" and "External latch position"

Only for EtherCAT: