"Index offset" specification for axis functions (Index group 0x4200 + ID)
Index offset (Hex) | Access | Axis type | Data type | Phys. unit | Definition range | Description | Note | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
0x00000001 | Write | every | VOID |
|
| Reset axis | For FIFO axes too! | ||||||||
0x00000002 | Write | every | VOID |
|
| Stop axis | For FIFO axes too! | ||||||||
0x00000003 | Write | every | VOID |
|
| Clear axis (task) | For FIFO axes too! | ||||||||
0x00000004 | Write | every | { |
|
| Emergency Stop (Emergency stop with regulated ramp) | Only for PTP axes! | ||||||||
REAL64 | e.g. mm/s^2 | > 0.0 | Deceleration (must be greater than or equal to the original deceleration) | ||||||||||||
REAL64 | e.g. mm/s^3 | > 0.0 | Jerk (must be greater than or equal to the original jerk) | ||||||||||||
} |
|
|
| ||||||||||||
0x00000005 | Write | PTP axis | { |
|
| Parametrized stop (with regulated ramp) | Only for PTP axes! Reserved function, no standard! | ||||||||
REAL64 | e.g. mm/s^2 | > 0.0 | Deceleration | ||||||||||||
REAL64 | e.g. mm/s^3 | > 0.0 | Jerk | ||||||||||||
} |
|
|
| ||||||||||||
0x00000009 | Write | PTP axis | { |
|
| Oriented stop (oriented end position) | Only for PTP axes! | ||||||||
REAL64 | e.g. degree | ≥ 0.0 | Modulo end position (modulo target position) | ||||||||||||
REAL64 | e.g. mm/s^2 | > 0.0 | Deceleration (not yet implemented) | ||||||||||||
REAL64 | e.g. mm/s^3 | > 0.0 | Jerk (not yet implemented) | ||||||||||||
} |
|
|
| ||||||||||||
|
|
|
|
|
|
|
| ||||||||
0x00000010 | Write | every | VOID |
|
| Reference axis ("calibration") |
| ||||||||
0x00000011 | Write | every | { |
|
| New end position axis |
| ||||||||
UINT32 | ENUM | s. appendix | End position type (see appendix) | ||||||||||||
REAL64 | e.g. mm | ±∞ | New end position (target position) | ||||||||||||
} |
|
|
| ||||||||||||
0x00000012 | Write | every | { |
|
| New end position and new velocity axis |
| ||||||||
UINT32 | ENUM | s. appendix | Command type (s. appendix) | ||||||||||||
UINT32 | ENUM | s. appendix | End position type (s. appendix) | ||||||||||||
REAL64 | e.g. mm | ±∞ | new end position (target position) | ||||||||||||
REAL64 | e.g. mm/s | ≥ 0.0 | New end velocity (requested travelling speed) | ||||||||||||
REAL64 | e.g. mm | ±∞ | Optional: Switching position from which the new travel profile is activated | ||||||||||||
} |
|
|
| ||||||||||||
0x00000015 | Write | every | { |
|
| New dynamic parameters for active positioning |
| ||||||||
REAL64 | e.g. mm/s^2 | > 0.0 | Acceleration | ||||||||||||
REAL64 | e.g. mm/s^2 | > 0.0 | Deceleration | ||||||||||||
REAL64 | e.g. mm/s^3 | > 0.0 | Optional: Jerk (not yet implemented) | ||||||||||||
} |
|
|
| ||||||||||||
0x00000016 | ReadWrite | every SERVO | Write (76 bytes) |
|
| Universal axis start (UAS): merge of single commands, such as axis start, and online changes in combination with "Buffer Mode" (see TcMc2.lib) | Always to SAF Port 501! | ||||||||
{ |
|
|
| ||||||||||||
UINT32 | ENUM | s. appendix | Start type (s. appendix) | ||||||||||||
UINT32 | 1 | ≥ 0 | Bit mask for checks and operation modes | ||||||||||||
REAL64 | e.g. mm | ±∞ | End position (target position) | ||||||||||||
REAL64 | e.g. mm/s | ≥ 0.0 | Required velocity Vrequ | ||||||||||||
REAL64 | e.g. mm/s^2 | ≥ 0.0 | Optional: Acceleration | ||||||||||||
REAL64 | e.g. mm/s^2 | ≥ 0.0 | Optional: Deceleration | ||||||||||||
REAL64 | e.g. mm/s^3 | ≥ 0.0 | Optional: Jerk | ||||||||||||
UINT32 | ENUM | s. appendix | |||||||||||||
REAL64 | e.g. mm | ±∞ | Optional: Blending position (command blending position) | ||||||||||||
REAL64 | e.g. mm/s | ≥ 0.0 | Optional: Segment start velocity Vi (0 ≤ Vi ≤ Vrequ) | ||||||||||||
REAL64 | e.g. mm/s | ≥ 0.0 | Optional: Segment end velocity Vf (0 ≤ Vf ≤ Vrequ) | ||||||||||||
} |
|
|
| ||||||||||||
Read |
|
|
| ||||||||||||
{ |
|
|
| ||||||||||||
UINT16 | 1 | ≥ 0 | Command number (job number) | ||||||||||||
UINT16 | 1 | ≥ 0 | Command status | ||||||||||||
} |
|
|
| ||||||||||||
0x00000017 | ReadWrite |
SERVO | Write (76 bytes) |
|
| "Master/slave decoupling" and "Universal axis start (UAS)": Merge of decoupling command of a slave axis (IdxOffset: 0x00000041) and the subsequent universal axis start (UAS) (IdxOffset: 0x00000016) | Not yet released! | ||||||||
{ |
|
|
| ||||||||||||
UINT32 | ENUM | s. appendix | Start type (s. appendix) | ||||||||||||
UINT32 | 1 | ≥ 0 | Bit mask for checks and operation modes | ||||||||||||
REAL64 | e.g. mm | ±∞ | End position (target position) | ||||||||||||
REAL64 | e.g. mm/s | ≥ 0.0 | Required velocity Vrequ | ||||||||||||
REAL64 | e.g. mm/s^2 | ≥ 0.0 | Acceleration | ||||||||||||
REAL64 | e.g. mm/s^2 | ≥ 0.0 | Deceleration | ||||||||||||
REAL64 | e.g. mm/s^3 | ≥ 0.0 | Jerk | ||||||||||||
UINT32 | ENUM | s. appendix | |||||||||||||
REAL64 | e.g. mm | ±∞ | Optional: Blending position (command blending position) | ||||||||||||
REAL64 | e.g. mm/s | ≥ 0.0 | Optional: Segment start velocity Vi (0 ≤ Vi ≤ Vrequ) | ||||||||||||
REAL64 | e.g. mm/s | ≥ 0.0 | Optional: Segment end velocity Vf (0 ≤ Vf ≤ Vrequ) | ||||||||||||
} |
|
|
| ||||||||||||
Read |
|
|
| ||||||||||||
{ |
|
|
| ||||||||||||
UINT16 | 1 | ≥ 0 | Command number (job number) | ||||||||||||
UINT16 | 1 | ≥ 0 | Command status | ||||||||||||
} |
|
|
| ||||||||||||
0x00000018 | Write | every | VOID |
|
| Release axis lock for motion commands (TcMc2) |
| ||||||||
0x00000019 | Write | every | UINT32 | 1 | > 0 | Set external axis error (runtime error) | Caution by using! | ||||||||
0x00n0001A | Write | every | { |
|
| Set actual axis position | Caution by using! For FIFO axes too! Always to SAF Port 501! | ||||||||
UINT32 | ENUM | s. appendix | Actual position type (s. appendix) | ||||||||||||
REAL64 | e.g. mm | ±∞ | Actual position for axis n = 0: standard encoder of the axis n > 0: n-th encoder for the axis (optional) | ||||||||||||
} |
|
|
| ||||||||||||
0x00n0001B | Write | every | UINT32 | 1 | 0/1 | Set reference flag ("calibrate flag") n = 0: standard encoder of the axis n > 0: n-th encoder for the axis (optional) | Caution by using! For FIFO axes too! | ||||||||
0x00n0001C | Write | SERVO | { |
|
| Set only actual axis position without manipulating the set position (also for slave and with active process) | Caution by using! | ||||||||
UINT32 | ENUM | s. appendix | Actual position type (s. appendix) | ||||||||||||
REAL64 | e.g. mm | ±∞ | Actual position for axis n = 0: standard encoder of the axis n > 0: n-th encoder for the axis (optional) Take care when using! | ||||||||||||
} |
|
|
| ||||||||||||
0x00n0001D | Write | every | { |
|
| Set actual value of the axis on the drive side (Position interface and encoder offset of null required!) n = 0: standard encoder of the axis n > 0: n-th encoder for the axis (optional) | Caution by using! Only for CANopen | ||||||||
UINT32 | ENUM | s. appendix | Actual position type (s. appendix) | ||||||||||||
REAL64 | e.g. mm | ±∞ | Actual position for axis | ||||||||||||
} |
|
|
| ||||||||||||
0x00n0001E | Write | every | { |
|
| Set a new encoder scaling factor on the fly (also when axis is in motion) | Caution by using! Always to SAF Port 501! | ||||||||
UINT32 | ENUM | 1 | Encoder scaling factor type 1: Absolute 2: Relative | ||||||||||||
REAL64 | e.g. mm/INC | [1.0E-8 ... 100.0] | New encoder scaling factor n = 0: standard encoder of the axis n > 0: n-th encoder for the axis (optional) | ||||||||||||
} |
|
|
| ||||||||||||
0x00n0001F | Write | every | { |
|
| Set actual axis position on the fly (also when axis is in motion) | Caution by using! Always to SAF Port 501! | ||||||||
UINT32 | ENUM |
| Position type for setting actual value on the fly 1: Absolute 2: Relative | ||||||||||||
UINT32 | 1 |
| Control DWord, e.g. for "clearing the position lag" | ||||||||||||
REAL64 |
|
| Reserve | ||||||||||||
REAL64 | e.g. mm | ±∞ | New actual axis position | ||||||||||||
UINT32 |
|
| Reserve | ||||||||||||
UINT32 |
|
| Reserve | ||||||||||||
} |
|
|
| ||||||||||||
|
|
|
|
|
|
|
| ||||||||
0x00000020 | Write | every 1D start | { |
|
| Standard axis start: |
| ||||||||
UINT32 | ENUM | s. appendix | Start type (s. appendix) | ||||||||||||
REAL64 | e.g. mm | ±∞ | End position (target position) | ||||||||||||
REAL64 | e.g. mm/s | ≥0.0 | Required velocity | ||||||||||||
} |
|
|
| ||||||||||||
0x00000021 | Write | every 1D start | { |
|
| Extended axis start (SERVO): |
| ||||||||
UINT32 | ENUM | s. appendix | Start type (s. appendix) | ||||||||||||
REAL64 | e.g. mm | ±∞ | End position (target position) | ||||||||||||
REAL64 | e.g. mm/s | ≥ 0.0 | Required velocity | ||||||||||||
UINT32 | 0/1 | 0/1 | Standard acceleration? | ||||||||||||
REAL64 | e.g. mm/s^2 | ≥ 0.0 | Acceleration | ||||||||||||
UINT32 | 0/1 | 0/1 | Standard deceleration? | ||||||||||||
REAL64 | e.g. mm/s^2 | ≥ 0.0 | Deceleration | ||||||||||||
UINT32 | 0/1 | 0/1 | Standard jerk? | ||||||||||||
REAL64 | e.g. mm/s^3 | ≥ 0.0 | Jerk | ||||||||||||
} |
|
|
| ||||||||||||
0x00000022 | Write | SERVO(MW) | { |
|
| Special axis start (SERVO): | Reserved start function, no standard! | ||||||||
UINT32 | ENUM | s. appendix | Start type (s. appendix) | ||||||||||||
REAL64 | e.g. mm | ±∞ | End position (target position) | ||||||||||||
REAL64 | mm/s | ≥ 0.0 | Required start velocity | ||||||||||||
REAL64 | e.g. mm | ±∞ | Position for a new velocity level | ||||||||||||
REAL64 | e.g. mm/s | ≥ 0.0 | New end velocity level | ||||||||||||
UINT32 | 0/1 | 0/1 | Standard acceleration? | ||||||||||||
REAL64 | e.g. mm/s^2 | ≥ 0.0 | Acceleration | ||||||||||||
UINT32 | 0/1 | 0/1 | Standard deceleration? | ||||||||||||
REAL64 | e.g. mm/s^2 | ≥ 0.0 | Deceleration | ||||||||||||
UINT32 | 0/1 | 0/1 | Standard Jerk? | ||||||||||||
REAL64 | e.g. mm/s^3 | ≥ 0.0 | Jerk | ||||||||||||
} |
|
|
| ||||||||||||
0x00000023 | Write | SERVO |
|
|
| Start external set value setting (setting by cyclic axis interface PLCtoNC) |
| ||||||||
UINT32 | ENUM | 1: Absolute | Start type | ||||||||||||
REAL64 | e.g. mm | ±∞ | New end position (target position) optional! | ||||||||||||
} |
|
|
| ||||||||||||
0x00000024 | Write | SERVO | VOID |
|
| Stop/disable external set value setting |
| ||||||||
0x00000025 | Write | SERVO | { |
|
| Start reversing operation for positioning (SERVO): |
| ||||||||
UINT32 | ENUM | 1 | Start type (default: 1) | ||||||||||||
REAL64 | e.g. mm | ±∞ | End position 1 (target position) | ||||||||||||
REAL64 | e.g. mm | ±∞ | End position 2 (target position) | ||||||||||||
REAL64 | 0/1 | 0/1 | Required velocity | ||||||||||||
REAL64 | s | ≥ 0.0 | Idle time | ||||||||||||
} |
|
|
| ||||||||||||
0x00000026 | Write | every | { |
|
| Start drive output: |
| ||||||||
UINT32 | ENUM | s. appendix | Output type (s. appendix) | ||||||||||||
REAL64 | e.g. % | ±∞ | Required output value (e.g. %) | ||||||||||||
} |
|
|
| ||||||||||||
0x00000027 | Write | every | VOID |
|
| Start drive output |
| ||||||||
0x00000028 | Write | every | { |
|
| Change the drive output: |
| ||||||||
UINT32 | ENUM | s. appendix | Output type (s. appendix) | ||||||||||||
REAL64 | e.g. % | ±∞ | Required output value (e.g. %) | ||||||||||||
} |
|
|
| ||||||||||||
0x00000029 | Write | every | VOID |
|
| Instantaneously adopt current override value and freeze until next override change! | Reserved function, no standard! | ||||||||
0x0000002A | Write | every | { |
|
| Calculate and set encoder offset | Reserved function, no standard! | ||||||||
0x0000002B | ReadWrite | every | WriteData: s. 'UAS' ReadData: s. 'UAS' |
|
| Stop external setpoint generator and continuous endless motion ('UAS': Universal axis start) | Reserved function, no standard! | ||||||||
|
|
|
|
|
|
|
| ||||||||
0x00000030 | Write | SERVO | { |
|
| Start section compensation (SERVO) |
| ||||||||
UINT32 | ENUM | s. appendix | Compensation type (s. appendix) | ||||||||||||
REAL64 | e.g. mm/s^2 | ≥ 0.0 | Max. acceleration increase | ||||||||||||
REAL64 | e.g. mm/s^2 | ≥ 0.0 | Max. deceleration increase | ||||||||||||
REAL64 | e.g. mm/s | > 0.0 | Max. increase velocity | ||||||||||||
REAL64 | e.g. mm/s | > 0.0 | Base velocity for the process | ||||||||||||
REAL64 | e.g. mm | ±∞ | Path difference to be compensated | ||||||||||||
REAL64 | e.g. mm | > 0.0 | Path distance for compensation | ||||||||||||
} |
|
|
| ||||||||||||
0x00000030 | ReadWrite | SERVO returns the real active values | { |
|
| Start section compensation (SERVO) Note: contained only in "TcMc2.lib" |
| ||||||||
UINT32 | ENUM | s. appendix | Compensation type (s. appendix) | ||||||||||||
REAL64 | e.g. mm/s^2 | ≥ 0.0 | => Max. acceleration increase <= Returns the implemented acceleration increase (new in "TcMc2.lib") | ||||||||||||
REAL64 | e.g. mm/s^2 | ≥ 0.0 | => Max. Deceleration increase <= Returns the implemented deceleration increase (new in "TcMc2.lib") | ||||||||||||
REAL64 | e.g. mm/s | > 0.0 | => Requested max. velocity of increase <= Returns the implemented velocity of increase | ||||||||||||
REAL64 | e.g. mm/s | > 0.0 | Base velocity for the process | ||||||||||||
REAL64 | e.g. mm | ±∞ | => Requested distance difference to be compensate <= Returns the implemented distance difference | ||||||||||||
REAL64 | e.g. mm | > 0.0 | => Requested max. distance for compensation <= Returns implemented distance | ||||||||||||
UINT32 | 1 | ≥ 0 | <= Returns Warning ID (e.g. 0x4243) | ||||||||||||
} |
|
|
| ||||||||||||
0x00000031 | Write | SERVO | VOID |
|
| Stop section compensation (SERVO) |
| ||||||||
0x00000032 | Write | SERVO | { |
|
| Start reversing operation with velocity steps (SERVO): (can be used to determine the velocity step response) |
| ||||||||
UINT32 | ENUM | 1 | Start type (default: 1) | ||||||||||||
REAL64 | e.g. mm/s | ±∞ | Required velocity 1 (negative values also allowed) | ||||||||||||
REAL64 | e.g. mm/s | ±∞ | Required velocity 2 (negative values also allowed) | ||||||||||||
REAL64 | s | > 0.0 | Travel time for velocity 1 and 2 | ||||||||||||
REAL64 | s | ≥ 0.0 | Idle time | ||||||||||||
UINT32 | 1 | 0, 1, 2, 3... | Optional: number of repetitions, Default "0": unlimited in time | ||||||||||||
} |
|
|
| ||||||||||||
0x00000033 | Write | SERVO | { |
|
| Sinus Oscillation Sequence - used as single sinus oscillation (sinus generator) - used as sinus oscillation sequence (e.g. for bode plot) |
| ||||||||
UINT32 | ENUM | 1 | Start type (fixed to start type 1 yet) | ||||||||||||
REAL64 | e.g. mm/s | > 0.0 | Base amplitude (e.g. 2.5 mm/s) | ||||||||||||
REAL64 | Hz | [0.0 .... 10.0] | Base frequency (e.g. 1.953125 Hz) | ||||||||||||
REAL64 | e.g. mm/s | ≥ 0.0 | Start amplitude at begin (e.g. 0.0 mm/s) | ||||||||||||
REAL64 | e.g. mm/REV | > 0.0 | Feed constant motor (per motor turn) (e.g. 10.0 mm/REV) | ||||||||||||
REAL64 | Hz | ≥ 1.0 | Frequency range: start frequency (e.g. 20.0 Hz) | ||||||||||||
REAL64 | Hz | ≤ 1/(2*dT) | Frequency range: stop frequency (e.g. 500.0 Hz) | ||||||||||||
REAL64 | s | > 0.0 | Step duration (e.g. 2.048s) | ||||||||||||
UINT32 | 1 | [1 ... 200] | Number of measurements (step cycles) (e.g. 20) | ||||||||||||
UINT32 | 1 |
| Number of parallel measurements (e.g. 1) not used yet! | ||||||||||||
} |
|
|
| ||||||||||||
0x00000034 | Write | SERVO | { |
|
| Phasing - Start Phasing - Stop Phasing |
| ||||||||
UINT32 | ENUM | 1 | Phasing Type: 1: ABSOLUTE 2: RELATIVE 4096: STOP | ||||||||||||
UINT32 | 1 | ≥ 0 | Control Mask | ||||||||||||
UINT32 | 1 | ≥ 0 | Master axis ID (multi master) | ||||||||||||
UINT32 |
|
| Reserve | ||||||||||||
REAL64 | e.g. mm | > 0.0 | Phase shift | ||||||||||||
REAL64 | e.g. mm/s | > 0.0 | Velocity | ||||||||||||
REAL64 | e.g. mm/s^2 | ≥ 0.0 | Acceleration | ||||||||||||
REAL64 | e.g. mm/s^2 | ≥ 0.0 | Deceleration | ||||||||||||
REAL64 | e.g. mm/s^3 | ≥ 0.0 | Jerk | ||||||||||||
REAL64[4] |
|
| Reserve | ||||||||||||
UINT32 |
|
| Reserve | ||||||||||||
UINT32 | 1 | ENUM | Buffer mode | ||||||||||||
REAL64 | e.g. mm | ±∞ | Blending position | ||||||||||||
} |
|
|
| ||||||||||||
0x00000040 (0x00n00040) | Write | Master/Slave coupling: (SERVO) | { |
|
| Master/slave coupling (SERVO): | Extension for "flying saw"! | ||||||||
UINT32 | ENUM | s. appendix | Slave type/coupling type (see appendix) | ||||||||||||
UINT32 | 1 | [1...255] | Axis ID of the master axis/group | ||||||||||||
UINT32 | 1 | [0...8] | Sub-index n of the master axis (default: value: 0) | ||||||||||||
UINT32 | 1 | [0...8] | Sub-index n of the slave axis (default: value: 0) | ||||||||||||
REAL64 | 1 | [±1000000.0] | Parameter 1: Linear: gearing factor FlySawVelo: Reserve FlySaw: abs. synchron position master [mm] | ||||||||||||
REAL64 | 1 | [±1000000.0] | Parameter 2: Linear: Reserve FlySawVelo: Reserve FlySawPos: abs. synchron position slave [mm] | ||||||||||||
REAL64 | 1 | [±1000000.0] | Parameter 3: Linear: Reserve FlySawVelo: angle of inclination in [DEGREE] FlySawPos: angle of inclination in [DEGREE] | Angle > 0.0 and £ 90.0 degree (parallel saw: 90.0 degree) | |||||||||||
REAL64 | 1 | [±1000000.0] | Parameter 4: Linear: Reserve FlySawVelo: gearing factor FlySawPos: gearing factor |
| |||||||||||
} |
|
|
| ||||||||||||
|
|
|
|
|
|
|
| ||||||||
0x00000041 | Write | Master/slave decoupling (SERVO) | VOID |
|
| Master/slave decoupling (SERVO) |
| ||||||||
0x00000041 | Write | Master/slave decoupling with configurable follow-up function (SERVO) | { |
|
| Master/slave decoupling with configurable follow-up function (e.g. new end position, new velocity, stop, E-stop) (SERVO) | Not yet released! | ||||||||
UINT32 | ENUM | Decoupling type (see appendix) | |||||||||||||
REAL64 | e.g. mm | ±∞ | Optional: New end position | ||||||||||||
REAL64 | e.g. mm/s | > 0.0 | Optional: New requested velocity | ||||||||||||
REAL64 | e.g. mm/s^2 | ≥ 0.0 (0: Default) | Optional: Acceleration for new end position, new velocity and emergency stop (E-stop) | ||||||||||||
REAL64 | e.g. mm/s^2 | ≥ 0.0 (0: Default) | Optional: Deceleration for new end position, new velocity and emergency stop (E-stop) | ||||||||||||
REAL64 | e.g. mm/s^3 | ≥ 0.0 (0: Default) | Optional: Jerk for new end position, new velocity and emergency stop (E-stop) | ||||||||||||
} |
|
|
| ||||||||||||
0x00000042 | Write | Master/Slave coupling Type: LINEAR (&SPECIAL) | { |
|
| Change of the coupling parameters (SERVO): |
| ||||||||
REAL64 | 1 | [±1000000.0] | Parameter 1: Linear: gearing factor | ||||||||||||
REAL64 | 1 | [±1000000.0] | Parameter 2: Linear: Reserve | ||||||||||||
REAL64 | 1 | [±1000000.0] | Parameter 3: Linear: Reserve | ||||||||||||
REAL64 | 1 | [±1000000.0] | Parameter 4: Linear: Reserve | ||||||||||||
} |
|
|
| ||||||||||||
0x00000043 | Write | Master/slave table coupling Type: TABULAR | { |
|
| Change of the table coupling parameters (SERVO): |
| ||||||||
REAL64 | mm | ±∞ | Slave position offset | ||||||||||||
REAL64 | mm | ±∞ | Master position offset | ||||||||||||
} |
|
|
| ||||||||||||
0x00000043 | Write | Master/slave table coupling Type: TABULAR | { |
|
| Change of the table coupling parameters (SERVO): | Also for "Motion Function" | ||||||||
REAL64 | mm | ±∞ | Slave position offset | ||||||||||||
REAL64 | mm | ±∞ | Master position offset | ||||||||||||
REAL64 | 1 | ±∞ (<> 0.0) | Slave position scaling | ||||||||||||
REAL64 | 1 | ±∞ (<> 0.0) | Master position scaling | ||||||||||||
} |
|
|
| ||||||||||||
0x00000043 | Write | Master/slave table coupling Type: TABULAR | { |
|
| Change of the table coupling parameters (SERVO): |
| ||||||||
REAL64 | mm | ±∞ | Slave position offset | ||||||||||||
REAL64 | mm | ±∞ | Master position offset | ||||||||||||
REAL64 | 1 | ±∞ (<> 0.0) | Slave position scaling | ||||||||||||
REAL64 | 1 | ±∞ (<> 0.0) | Master position scaling | ||||||||||||
REAL64 | e.g. mm | ±∞ | Absolute master activation position | ||||||||||||
} |
|
|
| ||||||||||||
0x00000044 | Write | Slave-Stop (SERVO) | VOID |
|
| Stop the "flying saw" (SERVO) | Only for "flying saw" | ||||||||
0x00000045 (0x00n00045) | Write | Master/slave table coupling (SERVO) | { |
|
| Master/slave table coupling (SERVO): |
| ||||||||
UINT32 | ENUM | s. appendix | Slave type/coupling type (s. appendix) | ||||||||||||
UINT32 | 1 | [1...255] | Axis ID of the master axis | ||||||||||||
UINT32 | 1 | [0...8] | Subindex n of the master axis (default: value: 0) | ||||||||||||
UINT32 | 1 | [0...8] | Subindex n of the slave axis (default: value: 0) | ||||||||||||
|
|
| SOLO TABLE SECTION | ||||||||||||
REAL64 | mm | ±∞ | Slave position offset (type: TABULAR) | ||||||||||||
REAL64 | mm | ±∞ | Master position offset (type: TABULAR) | ||||||||||||
UINT32 | 1 | [0,1] | Slave position absolute (type: TABULAR) | ||||||||||||
UINT32 | 1 | [0,1] | Master position absolute (type: TABULAR) | ||||||||||||
UINT32 | 1 | [1...255] | Table ID of the coupling table (type: TABULAR) | ||||||||||||
|
|
| MULTI-TABLE SECTION | ||||||||||||
UINT16 | 1 | [0...8] | Number of tables (type: MULTITAB) Note: misused as interpolation type for solo tables | ||||||||||||
UNIT16 | 1 | [0...8] | Number of profile tables (type: MULTITAB) | ||||||||||||
UNIT32[8] | 1 | [1...255] | Table IDs of the coupling tables (type: MULTITAB) | ||||||||||||
} |
|
|
| ||||||||||||
0x00000046 | Write | Master / slave multi-tables | UINT32 | 1 | [1...255] | Activation of correction table correction table ID |
| ||||||||
0x00000046 | Write | Master / slave multi-tables | { |
|
| Activation of correction table |
| ||||||||
UINT32 | 1 | [1...255] | Correction table ID | ||||||||||||
REAL64 | e.g. mm | ±∞ | Absolute master activation position | ||||||||||||
} |
|
|
| ||||||||||||
0x00000047 | Write | Master/Slave Multi-tables | UINT32 | 1 | [1..255] | Deactivation of profile table at end of cycle Table ID of the current monocyclic profile table |
| ||||||||
0x00000048 | ReadWrite | Master/Slave Multi-tables | Write: UINT32 | 1 | [1..255] | Read the last correction offset:+ Table ID of the correction table |
| ||||||||
Read: REAL32 | e.g. mm | ±∞ | Offset by departing the correction table with the according table ID | ||||||||||||
0x00000049 | Write | Master/slave table coupling Type: TABULAR | REAL64 | 1 | ±∞ | Change the slave table scaling Scaling factor of the slave table column |
| ||||||||
0x0000004A (0x00n0004A) | Write | Master/slave universal table coupling (SERVO) | { |
|
| Master/slave solo table coupling (SERVO): |
| ||||||||
UINT32 | ENUM | s. appendix | Slave type/coupling type (see appendix) | ||||||||||||
UINT32 | 1 | [1...255] | Axis ID of the master axis | ||||||||||||
UINT32 | 1 | [0...8] | Subindex n of the master axis (default: value: 0) | ||||||||||||
UINT32 | 1 | [0...8] | Subindex n of the slave axis (default: value: 0) | ||||||||||||
UINT32 | 1 | 1...255] | Table ID of the coupling table (type: TABULAR) | ||||||||||||
UINT32 | 1 |
| Tabular interpolation type | ||||||||||||
REAL64 | mm | ±∞ | Slave position offset (type: TABULAR) | ||||||||||||
REAL64 | mm | ±∞ | Master position offset (type: TABULAR) | ||||||||||||
REAL64 | mm | ±∞ | Slave position scaling (type: TABULAR) | ||||||||||||
REAL64 | mm | ±∞ | Master position scaling (Type: TABULAR) | ||||||||||||
UINT32 | 1 | [0,1] | Slave position absolute? | ||||||||||||
UINT32 | 1 | [0,1] | Master position absolute? | ||||||||||||
UINT32 | ENUM | s. appendix | Activation type of the change (NEW) 0: 'instantaneous' (default) 1: 'at master cam position' 2: 'at master axis position' 3: 'next cycle' | ||||||||||||
REAL64 | mm | ±∞ | Activation position (NEW) | ||||||||||||
UINT32 | ENUM | s. appendix | Master scaling type (NEW) 0: user defined (default) 1: scaling with auto offset 2: off | ||||||||||||
UINT32 | ENUM | s. appendix | Slave scaling type (NEW) 0: user defined (default) 1: scaling with auto offset 2: off | ||||||||||||
} |
|
|
| ||||||||||||
0x0000004B (0x00n0004B) | Write | Master / slave universal flying saw (SERVO) | { |
|
| Master/slave synchronizing coupling (SERVO): |
| ||||||||
UINT32 | ENUM | s. appendix | Slave type/coupling type (s. appendix) | ||||||||||||
UINT32 | 1 | [1...255] | Axis ID of the master axis | ||||||||||||
UINT32 | 1 | [0...8] | Subindex n of the master axis (default: value: 0) | ||||||||||||
UINT32 | 1 | [0...8] | Subindex n of the slave axis (default: value: 0) | ||||||||||||
REAL64 | 1 | ±∞ (<> 0.0) | Gearing factor | ||||||||||||
REAL64 | mm | ±∞ | Master synchron position | ||||||||||||
REAL64 | mm | ±∞ | Slave synchron position | ||||||||||||
REAL64 | mm/s | ≥ 0.0 | Slave velocity (optional) | ||||||||||||
REAL64 | mm/s^2 | ≥ 0.0 | Slave acceleration (optional) | ||||||||||||
REAL64 | mm/s^2 | ≥ 0.0 | Slave deceleration (optional) | ||||||||||||
REAL64 | mm/s^3 | ≥ 0.0 | Slave jerk (optional) | ||||||||||||
UINT32 | 1 | ≥ 0 | Bit mask for checks and operation modes (Default value: 0) | ||||||||||||
} |
|
|
| ||||||||||||
|
|
|
|
|
|
|
| ||||||||
0x0000004D (0x00n0004D) | Write | Master/slave table coupling Type: TABULAR | { |
|
| Change of the table scaling (SERVO): | Also for MF Reserved function, no standard! | ||||||||
UINT32 | ENUM | s. appendix | Activation type of the change 0: 'instantaneous' (default) 1: 'at master cam position' 2: 'at master axis position' 3: 'next cycle' | ||||||||||||
REAL64 | e.g. mm | ±∞ | Activation position | ||||||||||||
UINT32 | ENUM | s. appendix | Master scaling type 0: user defined (default) 1: scaling with auto offset | ||||||||||||
UINT32 | ENUM | s. appendix | Slave scaling type 0: user defined (default) 1: scaling with auto offset 2: off | ||||||||||||
REAL64 | e.g. mm | ±∞ | Master position offset | ||||||||||||
REAL64 | e.g. mm | ±∞ | Slave position offset | ||||||||||||
REAL64 | 1 | ±∞ (<> 0.0) | Master position scaling | ||||||||||||
REAL64 | 1 | ±∞ | Slave position scaling | ||||||||||||
} |
|
|
| ||||||||||||
|
|
|
|
|
|
|
| ||||||||
0x00000050 | Write | every | VOID |
|
| Deactivate complete axis (disable) |
| ||||||||
0x00000051 | Write | every | VOID |
|
| Activate complete axis (enable) |
| ||||||||
0x00000052 | Write | SERVO | { |
|
| Change of the active axis control loop (triple from encoder, controller and axis interfaces) with/without external set value setting: |
| ||||||||
UINT32 | 1 | ≥ 0 | Number/index of the axis control loop (Default value: 0) | ||||||||||||
UINT32 | ENUM | see appendix (>0) | Switch type for synchronization behavior 1: 'Standard' | ||||||||||||
REAL64 | 1 | ±∞ | Synchronization value for switching (optional) | ||||||||||||
UINT32 | 0/ 1 | 0/1 | External set value setting by means of axis interface? Note: not used so far! | ||||||||||||
} |
|
|
| ||||||||||||
|
|
|
|
|
|
|
| ||||||||
0x00000060 | Write | every | VOID |
|
| Deactivate drive output (disable) |
| ||||||||
0x00000061 | Write | every | VOID |
|
| Activate drive output (enable) |
| ||||||||
0x00000062 | Write | high/low | UINT16 | 1 | 0/1 | Release parking brake? 0: automatic activation (default) 1: mandatorily always released! Note: reset to '0' when resetting the axis! |
| ||||||||
|
|
|
|
|
|
|
| ||||||||
0x00000070 | Write | every | VOID |
|
| Return of the axis from, e.g. a 3D group to its own PTP group |
| ||||||||