Manual creation via the TwinCAT Engineering

Manual creation via the TwinCAT Engineering 1:

OEM certificates should only be used in a secure environment

Since generating an OEM application license requires handling of the OEM certificate and its password, the process should only be carried out in an environment that is protected against malicious software (= hardened, protected PC), in order to prevent the password for the OEM private key being accessed by malicious software.

The manual signing of a License Request File, and thus the creation of a License Response File, is done in the TwinCAT Engineering in the Software protection configurator.

1. Select the OEM certificate in the Certificates tab.
Manual creation via the TwinCAT Engineering 2:
2. Click on Sign License Request File.
An Explorer window opens.
3. Select the License Request File to be signed (extension: *.tclrq).
A password dialog opens.
Manual creation via the TwinCAT Engineering 3:
4. Enter the password and click on OK.
The License Request File is signed, and the result is stored as a License Response File (extension: *.tclrs). The License Response File now has to be transferred back to the Engineering PC or the control computer.