Library Recipe Management - RecipeManCommands
The methods of the function block RecipeManCommands from the library "Recipe Management" enable the recipes to be managed programmatically.
![]() | The application automatically creates recipe files with the name <Recipe>.<Recipe definition>.txtrecipe on the controller. They serve as a clipboard for reading and writing recipe variables. The option Save recipe changes to recipe files automatically on the tab Recipe Manager > General influences access to these files. |
![]() | If the option Save recipe changes to recipe files automatically is activated, the recipes of the definition in TwinCAT and the implicit recipe files on the controller are automatically kept identical. The changing of recipes then also leads to file accesses. |
Method CreateRecipe
This method creates a new recipe in the specified recipe definition. It subsequently reads the current PLC values into the new recipe and saves it as a recipe file with a standard name. The standard name is <Recipe>.<Recipe definition>.<Recipe extension>.

Inputs (VAR_INPUT)
Name | Data type | Description |
---|---|---|
RecipeDefinitionName | STRING | Name of the recipe definition |
RecipeName | STRING | Name of the recipe |
Return value
Name | Data type | Description |
---|---|---|
CreateRecipe | DWORD | ERR_RECIPE_DEFINITION_NOT_FOUND ERR_RECIPE_ALREADY_EXIST ERR_RECIPE_NOMEMORY ERR_NO_RECIPE_MANAGER_SET ERR_OK |
Method CreateRecipeNoSave
This method creates a new recipe in the specified recipe definition. It subsequently reads the actual values into the new recipe.

Inputs (VAR_INPUT)
Name | Data type | Description |
---|---|---|
RecipeDefinitionName | STRING | Name of the recipe definition |
RecipeName | STRING | Name of the recipe |
Return value
Name | Data type | Description |
---|---|---|
CreateRecipeNoSave | DWORD | ERR_RECIPE_DEFINITION_NOT_FOUND ERR_RECIPE_ALREADY_EXIST ERR_RECIPE_NOMEMORY ERR_NO_RECIPE_MANAGER_SET ERR_OK |
Method DeleteRecipe
This method deletes a recipe from the recipe definition.

Inputs (VAR_INPUT)
Name | Data type | Description |
---|---|---|
RecipeDefinitionName | STRING | Name of the recipe definition |
RecipeName | STRING | Name of the recipe |
Return value
Name | Data type | Description |
---|---|---|
DeleteRecipe | DWORD | ERR_RECIPE_DEFINITION_NOT_FOUND ERR_RECIPE_NOT_FOUND ERR_NO_RECIPE_MANAGER_SET ERR_OK |
Method DeleteRecipeFile
This method deletes the specified recipe file of a recipe. The recipe file must be stored under the standard name <Recipe>.<Recipe definition>.<Recipe extension>.

Inputs (VAR_INPUT)
Name | Data type | Description |
---|---|---|
RecipeDefinitionName | STRING | Name of the recipe definition |
RecipeName | STRING | Name of the recipe |
Return value
Name | Data type | Description |
---|---|---|
DeleteRecipeFile | DWORD | ERR_RECIPE_DEFINITION_NOT_FOUND ERR_RECIPE_NOT_FOUND ERR_RECIPE_FILE_NOT_FOUND ERR_NO_RECIPE_MANAGER_SET ERR_OK |
Method LoadAndWriteRecipe
The method loads a recipe from the specified recipe file. The recipe file must be stored under the standard name <Recipe>.<Recipe definition>.<Recipe extension>. It subsequently writes the recipe into the PLC variables.
![]() | Entries in the recipe file that contain no value assignment are not loaded and written. Refer to the description of the menu command Load and write Recipe. |

Inputs (VAR_INPUT)
Name | Data type | Description |
---|---|---|
RecipeDefinitionName | STRING STRING | Name of the recipe definition |
RecipeName | STRING | Name of the recipe |
Return value
Name | Data type | Description |
---|---|---|
LoadAndWriteRecipe | DWORD | ERR_RECIPE_DEFINITION_NOT_FOUND ERR_RECIPE_NOT_FOUND ERR_RECIPE_FILE_NOT_FOUND ERR_RECIPE_MISMATCH ERR_RECIPE_NOT_ALL_VARIABLES_WERE_LOADED ERR_NO_RECIPE_MANAGER_SET ERR_OK |
Method LoadFromAndWriteRecipe
This method loads the specified recipe file into a recipe. It subsequently writes the recipe into the PLC variables.
![]() | Entries in the recipe file that contain no value assignment are not loaded and written. Refer to the description of the menu command Load and write Recipe. |

Inputs (VAR_INPUT)
Name | Data type | Description |
---|---|---|
RecipeDefinitionName | STRING | Name of the recipe definition |
RecipeName | STRING | Name of the recipe |
FileName | STRING (255) | Name of the file |
Return value
Name | Data type | Description |
---|---|---|
LoadFromAndWriteRecipe | DWORD | ERR_RECIPE_DEFINITION_NOT_FOUND ERR_RECIPE_NOT_FOUND ERR_RECIPE_FILE_NOT_FOUND ERR_RECIPE_MISMATCH ERR_RECIPE_NOT_ALL_VARIABLES_WERE_LOADED ERR_NO_RECIPE_MANAGER_SET ERR_OK |
See also:
- TC3 User Interface documentation: Command Load and Write Recipe
Method LoadRecipe
The method loads a recipe from a recipe file. The recipe file must be stored under the standard name <Recipe>.<Recipe definition>.<Recipe extension>.
![]() | Entries in the recipe file that contain no value assignment are not loaded and written. Refer to the description of the menu command Load and write Recipe. |

Inputs (VAR_INPUT)
Name | Data type | Description |
---|---|---|
RecipeDefinitionName | STRING | Name of the recipe definition |
RecipeName | STRING | Name of the recipe |
Return value
Name | Data type | Description |
---|---|---|
LoadRecipe | DWORD | ERR_RECIPE_DEFINITION_NOT_FOUND ERR_RECIPE_NOT_FOUND ERR_RECIPE_FILE_NOT_FOUND ERR_RECIPE_MISMATCH ERR_RECIPE_NOT_ALL_VARIABLES_WERE_LOADED ERR_NO_RECIPE_MANAGER_SET ERR_OK |
See also:
- TC3 User Interface documentation: Command Load and Write Recipe
Method ReadAndSaveAs
This method reads the current PLC values from the variables of the recipe definition and saves this data set in a recipe file without changing the existing standard recipe file <recipe.recipedefinition.extension>.

Inputs (VAR_INPUT)
Name | Data type | Description |
---|---|---|
RecipeDefinitionName | STRING | Name of the recipe definition The variables specified in the recipe definition are read out. |
FileName | STRING(255) | Name of the file. The currently read-out data set is saved as a recipe in the file. |
Return value
Name | Data type | Description |
---|---|---|
ReadAndSaveAs | DWORD | ERR_RECIPE_DEFINITION_NOT_FOUND ERR_RECIPE_SAVE_ERR ERR_NO_RECIPE_MANAGER_SET ERR_OK |
Method ReadAndSaveRecipe
This method reads the current PLC values into the recipe. It subsequently saves the recipe to a recipe file with a standard name. The standard name is <Recipe>.<Recipe definition>.<Recipe extension>. The contents of any existing file are overwritten.

Inputs (VAR_INPUT)
Name | Data type | Description |
---|---|---|
RecipeDefinitionName | STRING | Name of the recipe definition |
RecipeName | STRING | Name of the recipe |
Return value
Name | Data type | Description |
---|---|---|
ReadAndSaveRecipe | DWORD | Return value, possible values: ERR_RECIPE_DEFINITION_NOT_FOUND ERR_RECIPE_NOT_FOUND ERR_RECIPE_SAVE_ERR ERR_NO_RECIPE_MANAGER_SET ERR_OK |
Method ReadAndSaveRecipeAs
This method reads the current PLC values into the recipe. It subsequently saves the recipe to a specified recipe file. The contents of any existing file are overwritten.

Inputs (VAR_INPUT)
Name | Data type | Description |
---|---|---|
RecipeDefinitionName | STRING | Name of the recipe definition |
RecipeName | STRING | Name of the recipe |
FileName | STRING | Name of the file |
Return value
Name | Data type | Description |
---|---|---|
ReadAndSaveRecipeAs | DWORD | Return value, possible values: ERR_RECIPE_DEFINITION_NOT_FOUND ERR_RECIPE_NOT_FOUND ERR_RECIPE_SAVE_ERR ERR_NO_RECIPE_MANAGER_SET ERR_OK |
Method SaveRecipe
This method saves the recipe to a recipe file with a standard name. The standard name is <Recipe>.<Recipe definition>.<Recipe extension>. The contents of any existing file are overwritten.

Inputs (VAR_INPUT)
Name | Data type | Description |
---|---|---|
RecipeDefinitionName | STRING | Name of the recipe definition |
RecipeName | STRING | Name of the recipe |
Return value
Name | Data type | Description |
---|---|---|
SaveRecipe | DWORD | ERR_RECIPE_DEFINITION_NOT_FOUND ERR_RECIPE_NOT_FOUND ERR_RECIPE_SAVE_ERR ERR_NO_RECIPE_MANAGER_SET ERR_OK |
Method ReadRecipe
This method reads the current PLC values into the recipe.

Inputs (VAR_INPUT)
Name | Data type | Description |
---|---|---|
RecipeDefinitionName | STRING | Name of the recipe definition |
RecipeName | STRING | Name of the recipe |
Return value
Name | Data type | Description |
---|---|---|
ReadRecipe | DWORD | ERR_RECIPE_DEFINITION_NOT_FOUND ERR_RECIPE_NOT_FOUND ERR_NO_RECIPE_MANAGER_SET ERR_OK Data server error from 16#2000 to 16#20FF Data source driver error from 16#2100 to 16#21FF |
Method WriteRecipe
This method writes the recipe into the PLC variables.

Inputs (VAR_INPUT)
Name | Data type | Description |
---|---|---|
RecipeDefinitionName | STRING | Name of the recipe definition |
RecipeName | STRING | Name of the recipe |
Return value
Name | Data type | Description |
---|---|---|
WriteRecipe | DWORD | ERR_RECIPE_DEFINITION_NOT_FOUND ERR_RECIPE_NOT_FOUND ERR_NO_RECIPE_MANAGER_SET ERR_OK |
Method ReloadRecipes
This method reads the list of recipes from a file system. Recipes with the standard name <Recipe>.<Recipe definition>.<Recipe extension> located in the path defined in the recipe manager are thereby considered.

Inputs (VAR_INPUT)
Name | Data type | Description |
---|---|---|
RecipeDefinitionName | STRING | Name of the recipe definition |
Return value
Name | Data type | Description |
---|---|---|
ReloadRecipes | DWORD | ERR_RECIPE_DEFINITION_NOT_FOUND ERR_NO_RECIPE_MANAGER_SET ERR_OK |
Method GetRecipeCount
This method returns the number of recipes in a recipe definition.

Inputs (VAR_INPUT)
Name | Data type | Description |
---|---|---|
RecipeDefinitionName | STRING | Name of the recipe definition |
Return value
Name | Data type | Description |
---|---|---|
GetRecipeCount | INT | ERR_RECIPE_DEFINITION_NOT_FOUND ERR_NO_RECIPE_MANAGER_SET ERR_OK |
Method GetRecipeNames
This method returns the recipe names in a recipe definition.

Inputs (VAR_INPUT)
Name | Data type | Description |
---|---|---|
RecipeDefinitionName | STRING | Name of the recipe definition |
pStrings | POINTER TO ARRAY [] OF STRING | Pointer to the array containing the recipe names. |
iSize | INT | Number of elements in the STRING array |
iStartIndex | INT | Start index Example: 1 |
Return value
Name | Data type | Description |
---|---|---|
GetRecipeNames | DWORD | Return value, possible values: ERR_RECIPE_DEFINITION_NOT_FOUND ERR_NO_RECIPE_MANAGER_SET ERR_OK |
Example:
There are 50 recipes, for example. If you wish to generate a table that displays 10 recipe names simultaneously, you must define a STRING array:
strArr: ARRAY[0..9] OF STRING;
Corresponding to the iStartIndex you then obtain the recipe names for the specified range.
iStartIndex := 0; die Namen 0..9 werden zurückgegeben
iStartIndex := 20; die Namen 20..29 werden zurückgegeben
The following applies in this example:
iSize := 10;
Method GetRecipeValues
This method returns the values of a recipe.

Inputs (VAR_INPUT)
Name | Data type | Description |
---|---|---|
RecipeDefinitionName | STRING | Name of the recipe definition |
RecipeName |
| Name of the recipe |
pStrings | POINTER TO ARRAY [] OF STRINGS | Pointer to a string in which the recipe values are stored. |
iSize | INT | Size of the string array. |
iStartIndex | INT | The start index. |
iStringLength | INT | The length of the string in the array. |
Return value
Name | Data type | Description |
---|---|---|
GetRecipeValues | DWORD | ERR_RECIPE_DEFINITION_NOT_FOUND ERR_RECIPE_NOT_FOUND ERR_NO_RECIPE_MANAGER_SET ERR_OK |
Example:
There are 50 recipes, for example. If you wish to generate a table that displays 10 recipe values simultaneously, you must define a STRING array:
strArr: ARRAY[0..9] OF STRING;
Corresponding to the iStartIndex you then obtain the recipe values for a specified range.
iStartIndex := 0; die Werte 0..9 werden zurückgegeben
iStartIndex := 20; die Namen 20..29 werden zurückgegeben
The following applies in this example:
iStringLength := 80;
iSize := 10;
Method GetRecipeVariableNames
This method returns the names of the recipe variables of a recipe.

Inputs (VAR_INPUT)
Name | Data type | Description |
---|---|---|
RecipeDefinitionName | STRING | Name of the recipe definition |
RecipeName |
| Name of the recipe |
pStrings | POINTER TO ARRAY [] OF STRINGS | Pointer to STRING data types in which the names of the recipe variables are stored. |
iSize | INT | Size of the STRING array. |
iStartIndex | INT | The start index. |
Return value
Name | Data type | Description |
---|---|---|
GetRecipeVariableNames | DWORD | ERR_RECIPE_DEFINITION_NOT_FOUND ERR_RECIPE_NOT_FOUND ERR_NO_RECIPE_MANAGER_SET ERR_OK |
Example:
There are 50 recipes, for example. If you wish to generate a table that displays 10 variable names of a recipe simultaneously, you must define a STRING array:
strArr: ARRAY[0..9] OF STRING;
Corresponding to the iStartIndex you then obtain the variable names of the recipe for the specified range.
iStartIndex := 0; die Namen 0..9 werden zurückgegeben
iStartIndex := 20; die Namen 20..29 werden zurückgegeben
The following applies in this example:
iSize := 10;
Method SetRecipeValues
This method sets the recipe values of a recipe.

Inputs (VAR_INPUT)
Name | Data type | Description |
---|---|---|
RecipeDefinitionName | STRING | Name of the recipe definition |
RecipeName |
| Name of the recipe |
pStrings | POINTER TO ARRAY [] OF STRINGS | Pointer to STRING data types in which the recipe values are stored. |
iSize | INT | Size of the STRING array. |
iStartIndex | INT | The start index. |
Return value
Name | Data type | Description |
---|---|---|
SetRecipeValues | DWORD | ERR_RECIPE_DEFINITION_NOT_FOUND ERR_RECIPE_NOT_FOUND ERR_NO_RECIPE_MANAGER_SET ERR_OK |
Example:
There are 50 recipes, for example. If you wish to generate a table that sets 10 recipe values simultaneously, you must define a STRING array:
strArr: ARRAY[0..9] OF STRING;
Corresponding to the iStartIndex you can then set the recipe values for a specified range.
iStartIndex := 0; Die Werte 0..9 werden gesetzt
iStartIndex := 20; Die Werte 20..29 werden gesetzt
The following applies in this example:
iStringLength := 80;
iSize := 10;
Method GetLastError
This method returns the last error of the preceding operation.

Return value
Name | Data type | Description |
---|---|---|
GetLastError | DWORD | Return value, possible values: ERR_NO_RECIPE_MANAGER_SET ERR_OK |
Method ResetLastError
This method resets the last error.

Return value
Name | Data type | Description |
---|---|---|
ResetLastError | DWORD | ERR_NO_RECIPE_MANAGER_SET ERR_OK |
Method SetStoragePath
This method is for setting the storage path for the recipe file. It overwrites the path specification in the dialog Storage of the recipe manager.

Inputs (VAR_INPUT)
Name | Data type | Description |
---|---|---|
stPath | STRING | File path, example:
|
Return value
Name | Data type | Description |
---|---|---|
stPath | BOOL | TRUE (path was set) FALSE Possible errors: ERR_OK ERR_NO_RECIPE_MANAGER_SET |
Return values
The return values of the functions described above are contained in the GVL ReturnValues.
These are InOut constants of the data type UDINT.
Name | Initialization value | Comment |
---|---|---|
ERR_OK | 16#0 | The operation was carried out successfully. |
ERR_FAILED | 16#1 | The operation failed. |
ERR_PARAMETER | 16#2 | Incorrect parameter |
ERR_NOTINITIALIZED | 16#3 | The data server object is not initialized. The data server is required if the recipe management is used in combination with TwinCAT HMI. |
ERR_NOTIMPLEMENTED | 16#C | The data server does not implement the interface IDataServer4 that is required if the recipe management is used in combination with TwinCAT HMI. |
ERR_NO_OBJECT | 16#10 | Not all variables of a recipe definition can be written via the data server. Only the valid variables are written. |
ERR_NOMEMORY | 16#11 | The data server does not have sufficient memory. |
ERR_RECIPE_FILE_NOT_FOUND | 16#4000 | The recipe file was not found. |
ERR_RECIPE_MISMATCH | 16#4001 | The contents of the recipe file do not match the current recipe. This error is only output if the storage type is textual (see editor Recipe Manager, tab Storage, Storage Type) and if a variable name in the file does not correspond to the variable name in the recipe definition. The recipe file is not loaded if this error occurs. Possible causes: A variable was removed from the recipe definition in the project. |
ERR_RECIPE_SAVE_ERR | 16#4002 | The storage procedure failed. Possible causes
|
ERR_RECIPE_NOT_FOUND | 16#4003 | The recipe does not exist. |
ERR_RECIPE_DEFINITION_NOT_FOUND | 16#4004 | The recipe definition does not exist. |
ERR_RECIPE_ALREADY_EXIST | 16#4005 | The recipe already exists in the recipe definition. Create a new recipe under a different name. |
ERR_NO_RECIPE_MANAGER_SET | 16#4006 | The global recipe manager has not been created. Possible cause:
|
ERR_RECIPE_NOT_ALL_VARIABLES_WERE_LOADED | 16#4007 | The recipe definition contains more variables than the recipe file. In this case the variable values of the recipe file will be written in any case. This is only for information, not actually an error. |
ERR_RECIPE_NOMEMORY | 16#4008 | The recipe definition has no free memory to create a new recipe. Possible causes
|
ERR_RECIPE_MANAGER_LOCKED_DURING_ONLINE_CHANGE | 16#4009 | The recipe manager was blocked during the online change. Possible causes: Some of the RecipeMan commands that should have been executed during an online change were not executed. |
ERR_SOURCE_EXHAUSTED | 16#40A0 | Used for UTF8 Helper |
ERR_TARGET_EXHAUSTED | 16#40A1 | Used for UTF8 Helper |
ERR_SOURCE_ILLEGAL | 16#40A2 | Used for UTF8 Helper |