To time
For each MC slave device, the To time determines when it should apply the output values received from the master device after the DP cycle start. MC slave devices can be synchronized with each other if the same value is set for the To time. This value must at least match the Equi-Cycle time plus a safety margin of around 200 microseconds. The To time can be calculated for all MC slave devices with the "Calculate MC-Times" button.