Start/stop PLC
Download
Requirements
Language / IDE | Extract the sample program |
|---|---|
C# / Visual Studio |
Description
The following program starts or stops run-time system 1 in the PLC:
C# program
static void Main(string[] args)
{
//Create a new instance of class TcAdsClient
TcAdsClient tcClient = new TcAdsClient();
try
{
// Connect to local PLC - Runtime 1 - TwinCAT 3 Port=851
tcClient.Connect(851);
Console.WriteLine(" PLC Run\t[R]");
Console.WriteLine(" PLC Stop\t[S]");
Console.WriteLine("\r\nPlease choose \"Run\" or \"Stop\" and confirm with enter..");
string sInput = Console.ReadLine().ToLower();
//Process user input and apply chosen state
do{
switch (sInput)
{
case "r": tcClient.WriteControl(new StateInfo(AdsState.Run, tcClient.ReadState().DeviceState)); break;
case "s": tcClient.WriteControl(new StateInfo(AdsState.Stop, tcClient.ReadState().DeviceState)); break;
default: Console.WriteLine("Please choose \"Run\" or \"Stop\" and confirm with enter.."); sInput = Console.ReadLine().ToLower(); break;
}
} while (sInput != "r" && sInput != "s");
}
catch (Exception ex)
{
Console.WriteLine(ex.Message);
Console.ReadKey();
}
finally
{
tcClient.Dispose();
}
}