Specification of the PLC services
This section includes services to access the PLC memory range (%M field).
Index Group | Index Offset | Access | Data type | Description | Remarks |
|---|---|---|---|---|---|
0x00004020 | 0x00000000- 0x0000FFFF | R/W | UINT8[n] | READ_M - WRITE_M PLC memory range(%M field).Offset is byte offset. |
|
0x00004021 | 0x00000000- 0xFFFFFFFF | R/W | UINT8 | READ_MX - WRITE_MX PLC memory range (%MX field).The low word of the index offset is the byte offset. The index offset contains the bit address calculated from the byte number *8 + bit number |
|
0x00004025 | 0x00000000 | R | ULONG | PLCADS_IGR_RMSIZE |
|
0x00004030 | 0x00000000- 0xFFFFFFFF | R/W | UINT8 | PLCADS_IGR_RWRB |
|
0x00004035 | 0x00000000 | R | ULONG | PLCADS_IGR_RRSIZE |
|
0x00004040 | 0x00000000- 0xFFFFFFFF | R/W | UINT8 | PLCADS_IGR_RWDB |
|
0x00004045 | 0x00000000 | R | ULONG | PLCADS_IGR_RDSIZE |
|