Spindle modes
Analog spindles
Generally, the following machine data [AXIS] is assigned when using analog spindles:
- The mode ACHSMODE_KEINE_AUTO_RPF must not be set in P-AXIS-00015 (achs_mode).
- P-AXIS-00156 (ref_ohne_nocken) == TRUE
- P-AXIS-00157 (ref_ohne_rev) == TRUE
Based on these settings, the following state graph applies:
Fig.9: State graph of the spindle modes for analog drivesDigital spindles
When digital spindles are used (SERCOS), pay attention to the following when setting the machine data [AXIS]:
- The mode ACHSMODE_KEINE_AUTO_RPF must be set in P-AXIS-00015 (achs_mode).
- Contrary to analog spindles, the setting of P-AXIS-00156 (ref_ohne_nocken) and P-AXIS-00157 (ref_ohne_rev) is irrelevant.
Based on these settings, the following state graph applies:
Fig.10: State graph of the spindle modes for digital drives (e.g. SERCOS)