Power measurement at a machine

WARNING

Risk of injury from electric shock!

Bring the bus terminal system into a safe, de-energized state before starting mounting, disassembly or wiring of the bus terminals!

Power measurement at a machine 1:

Connection of low power split-core transformers with current and voltage interfaces

Both low power transformers with current and voltage interfaces can be connected to the RJ45 connections X1 - X4.

  • When using small signal transformers from the SCL and SVL series, the transformer ratios are set automatically via the electronic nameplate.
  • When using transformers without an electronic nameplate, manual configuration via the “modules/slots” procedure is required.
Power measurement at a machine 2:Fig.12: Power measurement on a machine with EL3475 and low power transformers SCL and SVL
Power measurement at a machine 3:

Terminal fuse protection

  • The voltage measurement inputs are high-resistance; a minimum measuring current flows.
    The protection for the SVL connections must therefore be applied in accordance with the conductor cross-section used.
  • For current measurement inputs, the fuse protection must be adapted by the device to be measured. The secondary currents of the transformers are no longer fused (see fig.)
Power measurement at a machine 4:

**) FE as star point for 3-phase systems without neutral conductor

Depending on the current transformer used, in 3-phase systems without a neutral conductor FE must be connected as a star point as shown in the figure above.
Please observe the current transformer manufacturer's instructions!

Power measurement at a machine 5:

Negative power values

If negative power values are measured on a circuit, please check whether the associated current transformer circuit is connected correctly.