SCT74xx | General

Primary side

SCT74xx-xxxx

Thermal rated continuous current Icth

1.0 * IN

Rated short-time thermal current Ith

60 * IN/1 s (max. 100 kA)

Rated impulse current Idyn

2.5 * Ith

Rated frequency fR

50..60 Hz

Secondary side

SCT74xx-xxxx

Secondary rated current Isr

5 A

Overcurrent limiting factor

FS15

Operating conditions

SCT74xx-xxxx

Permissible ambient temperature range during operation

-5…+50°C

Permissible ambient temperature range during storage

-25…+70°C

Permissible relative humidity

5…85%

Operating height

Up to 1000 m

Protection class

IP20

Insulation characteristics

SCT74xx-xxxx

Rated insulation level Um

0.72/3/- kV

Insulation class

E

Insulation test voltage

3 kV, 1 min, Urms, 50 Hz (Um ≤ 0.72 kV)

General data

SCT74xx-xxxx

Max. Diameter conductor bushing primary conductor

80 mm x 160 mm

Connection technology secondary

Screw terminals M5x8

Conductor cross section secondary

4 mm² with ferrule
6 mm² massive

Size

4

Dimensions (W x H x D)

195 mm x 243 mm x 64 mm

Weight

3335 g

Markings, standards and regulations *)

SCT74xx-xxxx

Markings/Approvals

CE, EAC, UKCA

Flame rating

UL 94 V-2

Standards/Regulations

EN 61869-1; EN 61869-2; IEC 61010-1

*) Real applicable approvals/markings see type plate on the side (product marking).

SCT74xx dimensions, size 4

SCT74xx | General 1:Fig.23: Isometric view, top view; all dimensions in mm
SCT74xx | General 2:Fig.24: Right side view, front view, left side view; all dimensions in mm