Technical terms of current transformers

Term

Explanation

Primary rated current Ipr (alternative symbol IN)

Value of the rated current on the primary side

Secondary rated current Isr

Value of the rated current on the secondary side

Secondary signal

With small signal transformers, a voltage signal in the mV range (e.g. 333 mV) is output using an internal load.

Rated power Sr

Value of apparent power (in [VA]) that the transformer can deliver to the secondary circuit at secondary rated current and rated load

Rated frequency fR

Value of the rated frequency

Accuracy class

Indication that the measurement deviations are within specified limits under prescribed conditions of use.

Rated insulation level Um

Highest voltage; RMS value of the highest conductor-to-conductor voltage for which a measuring transformer is rated with respect to its insulation

The value of the rated insulation level is given in 3 values:

1. maximum value of the conductor-to-conductor voltage for which the insulation of the transformers is designed;
2. value of the rated short-duration power frequency withstand voltage (50 Hz, 1 min), with which the insulation safety of the devices is tested
3. value of the surge voltage level (this specification is mostly unoccupied here, since according to IEC 61869/1 a specification is only required for transformers with a conductor-to-conductor voltage of > 1.2 kV)

Overcurrent limiting factor (FS)

Ratio of rated limiting current to primary rated current.

Rated continuous thermal current Icth

Value of the continuous current in the primary winding at which the overtemperature does not exceed the value specified in the standard, with the secondary winding loaded with the rated load.

Rated short-time thermal current Ith

Value of short-time current for a limited time in the primary winding at which the overtemperature does not exceed the value specified in the standard, with the secondary winding loaded with the rated load.

Rated peak current Idyn

Maximum value of the primary current whose electromagnetic force effect does not cause electrical and mechanical damage to the current transformer with short-circuited secondary winding.

"Open-circuit voltage" of small signal current transformers

Due to the low measuring resistance, there is no dangerous "open-circuit voltage" with small signal transformers. It is therefore not necessary to short-circuit the secondary terminals.

"Open-circuit voltage" of classic current transformers (e.g. SCT transformers with 1 A and 5 A secondary signal)

WARNING Current transformers which are not directly connected to a load must be short-circuited on the secondary side for safety reasons!

A current transformer operated open on the secondary side induces very high peak voltage values at its secondary terminals. The magnitudes of these voltages can reach values of up to several kilovolts, depending on the dimensioning of the current transformer, and thus represent a danger to persons and the functional safety of the transformer. For safety reasons, open operation should generally be avoided in order to prevent magnetization of the core iron during secondary open operation.

Grounding of secondary terminals

According to DIN VDE 0141 (01/2000) paragraph 5.3.4, current and voltage transformers for rated voltages from Um = 3.6 kV must be earthed on the secondary side.
For low voltage (Um ≤ 1.2 kV), grounding is not required if the transformer housings do not have any metal surfaces that can be touched over a large area.