Technical terms of current transformers
Term | Explanation |
|---|---|
Primary rated current Ipr (alternative symbol IN) | Value of the rated current on the primary side |
Secondary rated current Isr | Value of the rated current on the secondary side |
Secondary signal | With small signal transformers, a voltage signal in the mV range (e.g. 333 mV) is output using an internal load. |
Rated power Sr | Value of apparent power (in [VA]) that the transformer can deliver to the secondary circuit at secondary rated current and rated load |
Rated frequency fR | Value of the rated frequency |
Accuracy class | Indication that the measurement deviations are within specified limits under prescribed conditions of use. |
Rated insulation level Um | Highest voltage; RMS value of the highest conductor-to-conductor voltage for which a measuring transformer is rated with respect to its insulation The value of the rated insulation level is given in 3 values:
|
Overcurrent limiting factor (FS) | Ratio of rated limiting current to primary rated current. |
Rated continuous thermal current Icth | Value of the continuous current in the primary winding at which the overtemperature does not exceed the value specified in the standard, with the secondary winding loaded with the rated load. |
Rated short-time thermal current Ith | Value of short-time current for a limited time in the primary winding at which the overtemperature does not exceed the value specified in the standard, with the secondary winding loaded with the rated load. |
Rated peak current Idyn | Maximum value of the primary current whose electromagnetic force effect does not cause electrical and mechanical damage to the current transformer with short-circuited secondary winding. |
"Open-circuit voltage" of small signal current transformers | Due to the low measuring resistance, there is no dangerous "open-circuit voltage" with small signal transformers. It is therefore not necessary to short-circuit the secondary terminals. |
"Open-circuit voltage" of classic current transformers (e.g. SCT transformers with 1 A and 5 A secondary signal) | A current transformer operated open on the secondary side induces very high peak voltage values at its secondary terminals. The magnitudes of these voltages can reach values of up to several kilovolts, depending on the dimensioning of the current transformer, and thus represent a danger to persons and the functional safety of the transformer. For safety reasons, open operation should generally be avoided in order to prevent magnetization of the core iron during secondary open operation. |
Grounding of secondary terminals | According to DIN VDE 0141 (01/2000) paragraph 5.3.4, current and voltage transformers for rated voltages from Um = 3.6 kV must be earthed on the secondary side. |