SCT23xx | General

Primary side

SCT23xx-xxxx

Thermal rated continuous current Icth

≤2000 A: 1,2 * IN

>2000 A: 1,0 * IN

Rated short-time thermal current Ith

60 * IN /1 s (max. 100 kA)

Rated impulse current Idyn

2,5 * Ith

Rated frequency fR

50..60 Hz

Secondary side

SCT23xx-xxxx

Secondary rated current Isr

1 A

Operating conditions

SCT23xx-xxxx

Permissible ambient temperature range during operation

-5…+50 °C

Permissible ambient temperature range during storage

-25 … +70 °C

Permissible relative humidi

5 … 85 %

Operating height

Up to 1000 m

Protection class

IP20

Insulation characteristics

SCT23xx-xxxx

Rated insulation level Um

1,2/6/- kV

Surge voltage resistance according to DIN EN 61439 1:2012-06

12 kV (1,2/50 µs)

Insulation class

E

Gerneral data

SCT23xx-xxxx

Max. Diameter conductor bushing primary conductor

43,7 mm

Rail dimensions primary conductor

50 mm x 12 mm / 40 mm x 30 mm

Connection technology secondary

CAGE CLAMP ®

Conductor cross section secondary

2,5 … 4 mm² / 14-12 AWG

Stripping length

9 – 10 mm / 0,37 in

Size

3

Dimensions (W x H x D)

85 mm x 105 mm x 52 mm

Weight

340 g

Standards and regulations

SCT23xx-xxxx

Approvals/Markings *)

CE, UL

Standards/Regulations

IEC 61869-1; IEC 61869-2

*) Real applicable approvals/markings see type plate on the side (product marking).

SCT23xx dimensions, size 3

SCT23xx | General 1:
Isometric view, top view; all dimensions in mm
SCT23xx | General 2:
Right side view, front view, left side view; all dimensions in mm

Conductor bushing of the primary conductor, size 3

Rail 1 [mm]

50 x 12

Rail 2 [mm]

40 x 30

Rail 3 [mm]

/

Round conductor [mm]

Ø 43,7