Power measurement at a machine
| |
Risk of injury from electric shock! Bring the bus terminal system into a safe, de-energized state before starting mounting, disassembly or wiring of the bus terminals! |
![]() | Connection of low power split-core transformers with current and voltage interfaces Both low power transformers with current and voltage interfaces can be connected to the RJ45 connections X1 - X4.
|
- The voltage is measured via a low power voltage transformer (e.g. from the Beckhoff SVL series) in the following example via the RJ45 connection X1.
- The current is measured by means of a low power split-core transformer, 3-channel current interface (e.g. from the Beckhoff SCL series) in the following example, the RJ45 connection X2.
![]() | Terminal fuse protection
|
![]() | **) FE as star point for 3-phase systems without neutral conductor Depending on the current transformer used, in 3-phase systems without a neutral conductor FE must be connected as a star point as shown in the figure above. |
![]() | Negative power values If negative power values are measured on a circuit, please check whether the associated current transformer circuit is connected correctly. |