MTBF

MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product.

The MTBF figure is a statistical representation of the likelihood of a device to fail. A MTBF figure of e.g. 1,000,000 h means that statistically one unit will fail every 100 hours if 10,000 units are installed in the field. However, it cannot be determined if the failed unit has been running for 50,000 h or only for 100 h.

For these types of units, the MTTF (Mean Time To Failure) value is the same value as the MTBF value.

 

Input 48Vdc

 

MTBF SN 29500,
IEC 61709

765,000 h

At 24 V, 10 A and 40°C

1,363,000 h

At 24 V, 10 A and 25°C

MTBF MIL HDBK 217F

 

358,000 h

At 10 A and 40°C; Ground Benign GB40

403,000 h

At 10 A and 25°C; Ground Benign GB25

66,000 h

At 10 A and 40°C; Ground Fixed GF40

90,000 h

At 10 A and 25°C; Ground Fixed GF25