Lifetime expectancy
The lifetime expectancy shown in the table indicates the minimum number of operating hours (service life) and is determined by the lifetime expectancy of the built-in electrolytic capacitors. The lifetime expectancy is stated in operating hours and is calculated according to the specifications of the capacitor manufacturer. The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15 years (131,400 h).
Any number exceeding this value represents a calculated theoretical lifetime which can be used to compare devices.
| Input 48Vdc |
|
|---|---|---|
Lifetime expectancy | 275,000 h | At 24 V, 5 A and 40°C |
117,000 h | At 24 V, 10 A and 40°C | |
70,000 h | At 24 V, 12 A and 40°C | |
788,000 h | At 24 V, 5 A and 25°C | |
327,000 h | At 24 V, 10 A and 25°C | |
197,000 h | At 24 V, 12 A and 25°C |