Lifetime expectancy
The lifetime expectancy shown in the table indicates the minimum number of operating hours (service life) and is determined by the lifetime expectancy of the built-in electrolytic capacitors. The lifetime expectancy is stated in operating hours and is calculated according to the specifications of the capacitor manufacturer. The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15 years (131,400h).
Any number exceeding this value represents a calculated theoretical lifetime which can be used to compare devices.
| Input 24Vdc |
|
|---|---|---|
Lifetime expectancy | 299 000h | At 24V, 5A and 40°C |
103 000h | At 24V, 10A and 40°C | |
56 000h | At 24V, 12A and 40°C | |
844 000h | At 24V, 5A and 25°C | |
292 000h | At 24V, 10A and 25°C | |
159 000h | At 24V, 12A and 25°C |