Efficiency and losses
| Input 24Vdc |
| |
---|---|---|---|
Efficiency | Typ. | 94.2% | At 24V, 10A |
Typ. | 93.7% | At 24V, 12A (Extra Power) | |
Average efficiency*) | Typ. | 94.3% | At 25% at 2.5A, 25% at 5A, |
Losses | Typ. | 1.75W | At no output load |
Typ. | 6.8W | At 24V, 5A | |
Typ. | 14.8W | At 24V, 10A | |
Typ. | 19.5W | At 24V, 12A |
*) The average efficiency is an assumption for a typical application where the power supply is loaded with 25% of the nominal load for 25% of the time, 50% of the nominal load for another 25% of the time, 75% of the nominal load for another 25% of the time and with 100% of the nominal load for the rest of the time.

Losses vs. output current at 24V output and 24Vdc input voltage, typ.