Input inrush current
Active inrush current limitation (NTCs that are bridged by a MOSFET) limits the inrush current after the input voltage is switched on.
The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on.
Input inrush current  | Max.  | 8A  | At +25°C ambient, cold start  | 
Max.  | 10A  | At +40°C ambient, cold start  | |
Typ.  | 6Apeak  | At +25°C ambient, cold start  | |
Typ.  | 8Apeak  | At +40°C ambient, cold start  | |
Inrush energy  | Max.  | 1A2s  | At +40°C ambient, cold start  | 

- Input: 24Vdc
 - Output: 24V, 10A, constant current load
 - Ambient: 25°C
 
- Input current: 2A / DIV
 - Input voltage: 5V / DIV
 - Output voltage: 5V / DIV
 - Time basis:100ms / DIV