Recommendations for redundancy mode
Recommendations for the configuration of redundant power supply systems:
- Use separate input circuit breakers for each power supply.
- Use three-phase power supplies in order to ensure functional reliability in case of failure of a phase.
- If you use single-phase power supplies, connect them if possible to different phases or mains circuits.
- Set the power supply to "Parallel Use" mode if this function is available.
- It is advantageous to set the output voltages of all power supplies to the same value.