Environment
| Environment | ||
|---|---|---|
| Operating temperature | -25 °C to + 70 °C | The operating temperature corresponds to the ambient or environmental temperature and is defined as the air temperature 2 cm below the device. | 
| Storage temperature | -40 °C to + 70 °C | For storage and transport | 
| Moisture | 5 to 95 % r.h. | IEC 60068-2-30 | 
| Oscillation, sinusoidal | 2–17.8 Hz: ±1.6 mm; | IEC 60068-2-6 | 
| Oscillation, any | 0.5 m²(s³) | IEC 60068-2-64 | 
| Impact | 30g 6 ms, 20g 11 ms | IEC 60068-2-27 | 
| Installation altitude | 0 to 6000 m | Approvals apply only up to 2000 m | 
| Overvoltage category | III | IEC 62103, EN 62477-1 | 
| II | IEC 62103, EN 62477-1, above an altitude of 2000 m | |
| Degree of pollution | 2 | IEC 62103, EN 62477-1, not conductive | 
| LABS compatibility | The device does not release any silicone or other LABS-critical substances and is suitable for use in painting plants. | |