Input inrush current

The power supply is equipped with an active inrush current limiting circuit that limits the input inrush current to a very low value after power-up and after short interruptions of the input voltage.

 

 

3AC 400 V

3AC 480 V

 

Input inrush current*

Max.

6 A peak

6 A peak

temperature-independent

Typ.

4.5 A peak

4.5 A peak

Inrush energy

Max.

1.5 A² s

1.5 A² s

Start-up delay

Typ.

500 ms

600 ms

 

* The charge current of the interference suppression capacitors during the first few microseconds after switching on is not taken into account.

Input inrush current 1:
Typical switch-on behavior at nominal load, 25°C ambient temperature