Input inrush current
The power supply is equipped with an active inrush current limiting circuit that limits the input inrush current to a very low value after power-up and after short interruptions of the input voltage.
  | 
  | 3AC 400 V  | 3AC 480 V  | 
  | 
|---|---|---|---|---|
Input inrush current*  | Max.  | 10 A peak  | 10 A peak  | temperature-independent  | 
typically  | 3 A peak  | 3 A peak  | ||
Inrush energy  | Max.  | 1 A² s  | 1 A² s  | |
Inrush delay  | typically  | 270 ms  | 220 ms  | 
  | 
* The charge current of the interference suppression capacitors during the first few microseconds after switching on is not taken into account.