Terminals and wiring

The terminals are designed to be finger-safe according to IP20 and are suitable for field or factory wiring.

Technical data

Input

Output

DC-OK signal

Connection cross-section

e*: max. 6 mm²

f*:  max. 4 mm²

a*: max. 4 mm² (d<2.8 mm)

e*: max. 6 mm²

f*:  max. 4 mm²

a*: max 4 mm² (d<2.8 mm)

e*: max. 6 mm²

f*:  max. 4 mm²

a*: max 4 mm² (d<2,8 mm)

Connection cross section (AWG)

e*: AWG 20-10

f*: AWG 20-10

a* AWG 20-10 (d<2.8 mm)

e*: AWG 20-10

f*: AWG 20-10

a* AWG 20-10 (d<2.8 mm)

e*: AWG 20-10

f*: AWG 20-10

a* AWG 20-10 (d<2.8 mm)

Strip length

10 mm / 0.4 inch

10 mm / 0.4 inch

10 mm / 0.4 inch

e* = solid wire
f* = stranded wire
a* = with ferrule

Wiring instructions:

Terminals and wiring 1:
Insert the wire, then turn the lever to release the wire: same procedure the other way round

Series connection of power supply units:

Series connection (looping from one power supply output to the next) is permitted as long as the average output current flowing through a connection pin does not exceed 27 A. For higher currents please use a separate distribution terminal strip as shown in Fig. Using distribution terminals.

Terminals and wiring 2:
Series connection of outputs; use of distribution terminals