EMC
The EMC behavior of the device is designed for applications in industrial environments as well as residential, commercial or small business environments. The output may be earthed or non-earthed.
The device was tested according to EN 61000-6-1, EN 61000-6-2, EN 61000-6-3 and EN 61000-6-4.
Without additional measures to reduce emissions at the output (e.g. by using a filter), the device is not suitable for supplying a local DC power network in residential, commercial or small business environments. There are no restrictions for local DC power networks in industrial environments.
EMC interference immunity  | 
  | ||
|---|---|---|---|
Strong transients  | VDE 0160  | Over the entire load range  | 1550V; 1.3ms  | 
EMC interference emission  | 
  | |
|---|---|---|
Cable-related interference emission, input lines  | EN 55011, EN 55022, FCC Part 15, CISPR 11, CISPR 22  | Class B  | 
Interference emission  | EN 55011, EN 55022  | Class B  | 
Harmonic input current  | EN 61000-3-2  | Class A requirements met  | 
Voltage fluctuations, flicker  | EN 61000-3-3  | Requirements met 1)  | 
This device complies with FCC Part 15. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must be able to deal with any interference received, including interference that may cause undesired operation.  | ||
1) Tested with constant current loads, non-pulsating
Switching frequencies  | ||
|---|---|---|
Main converter  | 80kHz to 140kHz  | Output load and input voltage dependent  |