Use in a tightly sealed enclosure

When the power supply is installed in a tightly sealed enclosure, the temperature inside the enclosure is higher than outside. In this case, the temperature inside the enclosure is considered the ambient temperature for the power supply.

In the following test arrangement, the device is placed at the center of the enclosure, and there are no other heat-generating objects in the enclosure. The load is placed outside the box.

The temperature sensor inside the box is placed at the center of the right side of the power supply at a distance of 1 cm.

The following measurement results can be used as a reference to estimate the temperature rise within the enclosure.

 

Case A

Case B

Housing size

180x180x165mm Rittal housing, protection class IP66 PK 9519 100, plastic

180x180x165mm Rittal housing, protection class IP66 PK 9519 100, plastic

Input voltage

3x 400Vac

3x 400Vac

Load

24V, 8A; (=80%)

24V, 10A; (=100%)

Temperature inside the housing

48.4°C

54.7C

Temperature outside the housing

24.5°C

24.9°C

Temperature increase

23.9K

29.8K