Hold-up time

The hold-up time is the time during which the output voltage of a power supply remains within the specification after a loss of input power. The hold-up time depends on the output load. Without load the hold-up time can be up to several seconds. The green DC-OK LED is also on during this time.

 

 

AC 100 V

AC 120 V

AC 230 V

 

 

Hold-up time

Typ.

65 ms

65 ms

65 ms

At 48 V, 5 A, see Fig. Hold-up time vs. input voltage

Min.

54 ms

54 ms

54 ms

At 48 V, 5 A, see Fig. Hold-up time vs. input voltage

Typ.

32 ms

32 ms

32 ms

At 48 V, 10 A, see Fig. Hold-up time vs. input voltage

Min.

24 ms

24 ms

24 ms

At 48 V, 10 A, see Fig. Hold-up time vs. input voltage

Hold-up time 1:Fig.8: Hold-up time vs. input voltage; Shut-down behavior, definitions