Switching output via EtherCAT
Switching the outputs when the system is at a standstill or in the event of an error via "Disable output" The output voltage of the device can be disabled via "Disable output". In the event of a system standstill or fault, the power supply and corresponding downstream system components can be switched off and on again via TwinCAT in a targeted and location-independent manner. |
- 1. Enable the PDO 0x1600 "PSU Outputs" via the "Process data" tab
- "Disable output" is displayed in the tree structure. The power supply output can be disabled via the "Disable output" bit.
- 2. Restarting the EtherCAT system or reloading the configuration in Config mode (F4) restarts the EtherCAT communication and the process data is transferred.
- 3. If the "Disable output" bit is set to TRUE, the DC output voltage of the device is switched off.
- The output remains disabled as long as "Disable output" = TRUE.
- The voltage at the output returns when the "Disable output" bit is disabled again.
Enabling "Disable Output" via the Process Data tab using the PS2001-2420-1001 as an example