Information - diagnostic data
Index A000 PSU Diag data
Index (hex) | Name | Meaning | Data type | Flags | Default |
---|---|---|---|---|---|
A000:0 | PSU Diag data |
| UINT8 | RO | 0x20 (32dec) |
A000:11 | Max output voltage | Maximum output voltage in V.
| REAL32 | RW | 0x00000000 (0dec) |
A000:12 | Max output current | Maximum output current in A.
| REAL32 | RW | 0x00000000 (0dec) |
A000:13 | Actual output voltage | Value of the current output voltage in V | REAL32 | RO | 0x00000000 (0dec) |
A000:14 | Actual output current | Value of the current output current in A | REAL32 | RO | 0x00000000 (0dec) |
Index F914 PSU Info data
Index (hex) | Name | Meaning | Data type | Flags | Default |
---|---|---|---|---|---|
F914:0 | PSU Info data |
| UINT8 | RO | 0x14 (20dec) |
F914:12 | Operating time:Operating time | Total operating time of the device in s | UINT32 | RO | 0x00000000 (0dec) |
F914:13 | Uptime | Operating time since last AC-side switch-on process in s (cannot be reset) | UINT32 | RO | 0x00000000 (0dec) |
F914:14 | Turn on counter | Total number of AC-side turn-on operations of the power supply during the complete operating time (cannot be reset) | UINT32 | RO | 0x00000000 (0dec) |
Index FA14 PSU Diag data
Index (hex) | Name | Meaning | Data type | Flags | Default |
---|---|---|---|---|---|
FA14:0 | PSU Diag data |
| UINT8 | RO | 0x14 (20dec) |
FA14:11 | Min input voltage | Minimum RMS input voltage in VRMS. The value is updated again if it falls below the old value. The input voltage averaged over 10 mains periods is used as the reference value. Undervoltages due to a grid disconnection are not taken into account. | UINT32 | RW | 0x00000000 (0dec) |
FA14:12 | Input undervoltage counter | Number of undervoltage events of the RMS input voltage. | UINT16 | RW | 0x0000 (0dec) |
FA14:13 | Max input voltage | Maximum RMS input voltage in VRMS. The value is updated again if the old value is exceeded. The input voltage averaged over 10 mains periods is used as the reference value. | UINT32 | RW | 0x00000000 (0dec) |
FA14:15 | Max peak input voltage | Maximum peak input voltage from 0 V to 700 V. The value is updated again if the old value is exceeded. | REAL32 | RW | 0x00000000 (0dec) |
FA14:16 | Input overvoltage counter | Number of overvoltage events of the RMS input voltage. The counter for the input overvoltages is also increased if fast input voltage transients such as the VDE 0160 pulse or a surge pulse (EN 61000-4-5) occur. | UINT16 | RW | 0x0000 (0dec) |
FA14:17 | Min temperature | Minimum internal device temperature in °C. The value for the minimum device temperature is updated again if it falls below the old value. | REAL32 | RW | 0x00000000 (0dec) |
FA14:18 | Max temperature | Maximum internal device temperature in °C. The value for the maximum device temperature is updated again if the old value is exceeded. | REAL32 | RW | 0x00000000 (0dec) |
FA14:19 | Actual RMS input voltage | RMS value of the current input voltage in VRMS. | REAL32 | RO | 0x00000000 (0dec) |
FA14:1B | Actual temperature | Value of the current internal device temperature in °C | REAL32 | RO | 0x00000000 (0dec) |
All values of object 0xFA14 with flag: "RW"
|
Index F000 Modular Device profile
Index (hex) | Name | Meaning | Data type | Flags | Default |
---|---|---|---|---|---|
F000:0 | Modular Device Profile | General information for the Modular Device Profile | UINT8 | RO | 0x02 (2dec) |
F000:01 | Index distance | Index distance of the objects of the individual channels | UINT16 | RO | 0x0010 (16dec) |
F000:02 | Maximum number of modules | Number of channels | UINT16 | RO | 0x0001 (1dec) |
Index F008 Code word
Index (hex) | Name | Meaning | Data type | Flags | Default |
---|---|---|---|---|---|
F008:0 | Code word |
| UINT32 | RW | 0x00000000 (0dec) |
Index F081 Download revision
Index (hex) | Name | Meaning | Data type | Flags | Default |
---|---|---|---|---|---|
F081:0 | Download revision |
| UINT8 | RO | 0x01 (1dec) |
F081:01 | Revision number |
| UINT32 | RW | 0x00000000 (0dec) |