Input data

Index 6000 PSU Inputs

Index (hex)

Name

Meaning

Data type

Flags

Default

6000:0

PSU Inputs

 

UINT8

RO

0x16 (22dec)

6000:01

Warning

Is set if one of the following conditions applies:

  • The output voltage (0x6000:11) falls below the DC OK threshold (0x8000:16)
  • The output voltage (0x6000:11) exceeds the overvoltage threshold (0x8000:14)
  • The output current (0x6000:12) exceeds the overcurrent threshold (0x8000:15)
  • The internal device temperature (0xFA14:1B) exceeds the internal temperature threshold (0xF814:11)
  • The input voltage "Actual RMS input voltage" (0xFA14:19) falls below the minimum value of the nominal input voltage
  • The device has been disconnected from the power supply
  • If the warning bit = 1, the cause of the warning can be viewed in the Diag History or via the TwinCAT EventLogger.

BOOLEAN

RO

0x00 (0dec)

6000:02

Error

Becomes TRUE and results in the output voltage being switched off if one of the following conditions applies:

  • Device-specific overvoltage protection active
    The output voltage has exceeded the maximum permissible value. See chapter Protective functions.
  • Device-specific overcurrent protection active.
    The device was switched off due to the hiccup mode.
    The error bit is an image of the on/off behavior of the hiccup mode.
  • Device-specific overtemperature protection active.
    The internal device temperature has exceeded the maximum permissible value (130°C).
  • If the error bit = 1, the cause of the error can be viewed in the Diag History or via the TwinCAT EventLogger.

BOOLEAN

RO

0x00 (0dec)

6000:04

DC OK

The output voltage (0x6000:11) falls below the DC OK threshold (0x8000:16)

BOOLEAN

RO

0x00 (0dec)

6000:11

Output voltage

Current output voltage in V
Accuracy: typ. ±0.2% FSV (full scale value, typ. 0 to 65 V)

REAL32

RO

0x00000000 (0dec)

6000:12

Output current

Current output current in A
Accuracy: typ. ±0.2% FSV (full scale value, typ. 0 to 65 A)

REAL32

RO

0x00000000 (0dec)

6000:15

Info data 1

Synchronous information (selection via subindex 0x8001:19)

UINT16

RO

0x0000 (0dec)

6000:16

Info data 2

Synchronous information (selection via subindex 0x8001:21)

UINT16

RO

0x0000 (0dec)

Index F614 PSU Inputs

Index (hex)

Name

Meaning

Data type

Flags

Default

F614:0

PSU Inputs

 

UINT8

RO

0x03 (3dec)

F614:03

Input undervoltage

The input voltage "Actual RMS input voltage" (0xFA14:19) falls below the minimum value of the nominal input voltage.

BOOLEAN

RO

0x00 (0dec)